Laserfiche WebLink
cloud is part of the sanctuary. No change in building <br />envelope see section A3.1 & S2.3 & 12 /S3.1. <br />Energy <br />�� 1. PIE�ase show lighting reduction controls on the drawings, per WSEC C405.2.1.2. <br />C�se Engineers Response: Exception 2-All areas are controlled by <br />� occupant-sensing device. <br />2. Please show additional lighting controls on the drawings, per WSEC C405.2.2. <br />C��se Engineers Response: Each area will have manual controls. <br />�J Corridors will be switched remotely for security. <br />6. The new attic in the church will require insulation, per WSEC C101.4.3, to meet <br />the R-value shown in WSEC table C402.2. <br />SNBA Response: The "attic" has been eliminated, the ceiling cloud is <br />12" from the roof, the space above the cloud is part of <br />the sanctuary. No change in building envelope. See <br />section A3.1 & S2.3 & 12 /S3.1. <br />Mechanical-Deferred Submittal <br />1. The modified volume of the sanctuary and the basement meeting room should <br />be shown to be in compliance with the outside air and mechanical ventilation <br />requirements of IMC section 403. <br />S�BA Response: Outdoor ventilation requirements are added to plans <br />see sheet A2.3 & A2.4. <br />Respectfully Yours, <br />Stephen Wood <br />Architect <br />Eastlake� Community Church 4 of 4 Aug. 28, 2013 <br />B1307-015 <br />