Laserfiche WebLink
Treys Test File February 19,2014 <br /> Unit Dimensions -Split System Air Conditioning Units (Small) <br /> Item: Al Qty: 1 Tag(s): OU/IU-18 <br /> 'ELECTRICAL/GENERAL DATA <br /> 'GENERAL POWER CONN. COMPRESSOR <br /> Model: '4TWR7024* MirrmumCircuit Ampacity '15.0 Number: '1 <br /> Unit Primary Voltage: '208 Maximum Circuit Breaker: 25.0 Phase: 1 <br /> Unit Seccndary Voltage 230 Minimum Protection Rating: 25.0 Rated Load Amps: 11.7 <br /> Unit Hertz: 60 Locked Rotor Amps: 58.3 <br /> Unit Phase: 1 <br /> OUTDOOR MOTOR NOTES: <br /> Number: '1 1.Certified n accordance with the UnitaryAir-Conditionerequipment certification program which is based cn <br /> Horsepower: 0.125 AHRI Standard210/240. <br /> Motor Speed(RPM): 835 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. <br /> Phase: 13.Standard line lengths-60.Standard lift-60'Suction and Liquid line. <br /> Full LoadAmps: 0.74 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 <br /> Locked Rotor Amps: - 4.*=15,20,25,30,40 and 50 foot lineset available. <br /> REFRIGERANT <br /> Type: 'R410A <br /> Charge 10.2 lb <br /> Line Size O.D.Gas: 5/8" <br /> Line SizeO.D.LIQ: 3/8" <br /> Cl <br /> WEIGHT <br /> SHIPPING: 272.0 lb <br /> NET: 236.0 lb W <br /> (0 <br /> NOTES: <br /> Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED = <br /> FOR AT LEAST 60" ABOVE UNIT <br /> C2.PLACE UNIT FROM WALL <br /> C3.PLACE SHRUBBERY AT LEAST 12" C4 <br /> FROM UNIT ON TWO SIDES,OTHER SIDES <br /> UNRESTRICTED <br /> C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT <br /> FALL DIRECTLY ON UNIT <br /> 64111.11111) <br /> 1.1111111111 <br /> N <br /> C3 <br /> �C2 <br /> C3 <br /> WEIGHT AND CLEARANCE <br /> FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal "Pegg <br /> Installed by Others <br />