Laserfiche WebLink
Design nos <br />April 16, 2004 <br />Jeff Heilman, Development Technician <br />ReRick Pearson, 410 Beech St, <br />Plan Check C0404-001 <br />1915 Madison Street <br />Everett, Washington 98203 <br />Phone (425)353-0531 <br />Fax. (425) 353-6086 <br />www designlines.corn <br />Greetings Jeff, Rick brought his plans in to fix your concerns. I added / checked a few extra things <br />1 4x12 was overspanned. Revised column spacing, footings on foundation plan, sheet 9. <br />2. Showed bath layout, actually added wall thickness. Sheet 4. <br />3 Exhaust fan shown, venting to exterior noted. Sheet 4 <br />4. 110 volt detector shown in new bedroom, others shown in each bedroom and hall. Note added regarding <br />detectors. On floor plan, sheet 4. <br />5 Safety glass noted for new glass doors and window over soaking tub. Sheet 4 <br />6 Hip master girder truss noted at standard eight feet back, on roof fra, ing plan, sheet 10 Ends of girder <br />came down on window headers, Calculated and will provide printout of calculations for window headers. <br />7. You have done a fine job of noting the requirements for the insulation baffle, sheet 12. 1 have added <br />"insulation baffle" and an arrow on the same sheet. <br />All of the changes,/ additions are done in green <br />I only have been provided with one set — was there another? <br />Let me or Rick know if you have any other concerns, <br />Dexter Taylor Buz <br />ilding designer (/ ..c, <br />