DUAL INITIATING 20NE MODULE� SINGLE RELAY M�VJULE �
<br /> The Dual Zone Motiule (DZM) provides alarm and trouble LED The Single Relay Module (SRM) provides two (2) Form C
<br /> indicators for two (2) initiating zones with a disable switch for contacts for Zone 1 output (5 amperes @ 28 VDC/120 VAC)
<br /> each. It may be wired (or Class "A" (emergency) or"6" since the Common Control Assembly (CCA�3) alarm contacts
<br /> � � operation, and includes supervised outputs for reroote alarm and become system alarm conWcts when multiple zones are used. As
<br /> i �. trouble annunciation. Smoke detectors (including selected with the Auxiliary Signal Circuit (ASC�,the SRM snaps into the
<br /> two�wire types), heat detectors, waterilow switches, and other track located above the CCA-3, and is connected m the CCA•3
<br /> initiating devices may be used together on the tame zone without using a plug. . , �w
<br /> the use af limiting resistors. � ��-�
<br /> DUAL RELAY MODULE
<br /> The Dual Relay Module (DRM) provides two(2) Form C contacts - � '�
<br /> DUAL INITIATING/INDICATING ZONE MODULE Per zone,and is used in conjunction with the Dual Zone Module y
<br /> (DZM�, Cross Zone Module (CZM1, and/or Dual Initiating/ �'�
<br /> The Dual Initiating and Indicating Zone Module �DZS) allows Indicating Zone Modules (DZ5)when alarm contacts are needed � ''
<br /> , each initiating zone ro function also as an indicating zone. By tor control of zono-related functions. �, "
<br /> combining the same zone card as the one used on the Dual Zone :=,j
<br /> Module,with a unique terminal board, this module will provide � ,;-iF
<br /> . either floor above/iloor belew, ring�byzone, or general alarm � w pl�CT� . .,�,� J
<br /> � -;
<br /> modes of operation. FVU G 1 � �a �3:ones � zi r'i
<br /> Current-limited or polarized devices such as smoke detectors or ��l�,�
<br /> �' audible signal appliances,or the patented ESL Serics 420FS or
<br /> 425FS pboroelectronic smoke detectors may be used together on t w s:000: >;�
<br /> � each circuit. This allows greater distribution oi the alarm signal "'' � -;,�
<br /> ..t' i
<br /> . and reduces instal�ation time and system cost. t m 5:o�,e: �„�:;�1
<br /> ,� ��i, Aiarm and trouble indicamrs and a disable switch tor each zone �
<br /> :k_ ��`W
<br /> G are provided.The DZS may be wired for Class"A" (emergency) ; . .,,�.,
<br /> �? or "8" operetion, and includes supervised outputs for remote `,i�; �:4��°�
<br /> +� alarm and trouble annunciation. [ach circuit may support a .
<br /> 31 maximum of 1 ampere of alarm indicating devices. �'`�
<br /> � _ ,``:�;�'
<br /> _ �.�
<br /> F . .� CROSS ZONE DELAY RELEASE MODULE '
<br /> ,
<br /> The Cros:Zone Module (CZM) provides tor chemical suppression �
<br /> � ageM release. The module features the following: a supervised Three cabinets are availa�le to allow construction oi a system to
<br /> circuit (Class "A" or "B") for polarized releasing devices; meet the exact needs of the ins;allation. All cabinets are of the
<br /> automatic time delay of release capability;a 1 ampere indicating same width,and include wide wiring channels for quick and neat
<br /> circuit (Class"A"or"B") tor 24 VDC polarized si9naling devices; system wiring. All switches and status indicators are secured .
<br /> Class"B"supervised manual release and abort circuits;two(2) �ehind a locked door with a viewing window, preventing _ '����y
<br /> unauthorized entry to the system's manual functio�is.
<br /> Form C contact sets (rated 5 amperes @ 26 VDC/120 VAC ' .��
<br /> resistive�. The cabinets are keyed to the ESL Series 103 manual stations.
<br /> A tull LED indication of all circuit tunctions and trouble All cabinets are constructed of heavy-gauge steel with a red-
<br /> conditions is provided. The CZM works in partnership with a orange, texwred tini:h,and include the backbox and a detachable � --s,'j
<br /> separately ordered Dual Zone Module IDZM�. door assembly wiih key lock.The 6ack of each cabinet is dimpled
<br /> Tlie CZM occupies the space oi a DZM. It consists ot a plug�in to compensate tor uneven mounting surfaces.Cabinet dimensions .
<br /> electronics card,a terminal board,and its unique faceplate. are as follows:
<br /> DIMENSIONS ,
<br /> AUXILIARY POWER SUPPLY AND DUAL Model CA: i9.38" high x 21.50" wide x 5.25" deep
<br /> INDICATING CIRCUIT MODULE Model Ce: 23.88" high x 21.50" wide x 5.25" deep
<br /> The Auxiliary Power Supply and Duai Indicating Cii�uit Module Model CC: 28,38" high x 21.50" wide x 5.25" deep
<br /> (AP5) provides a 3 ampere,auxiliary power sup�ly and two (2)
<br /> supervised alarm indicating circuits. The assemhly coines Each cabinet requires the use of a Common Control Assembly
<br /> complete with a plug�in electronics card, a terminal board for (CCA-31.Model CA may be expanded to a maximum of five (5)
<br /> field wiring,a transformer,and a cabinet faceplate.This module initiating zones. Model CB may be expanded to a maximum of
<br /> requires thc spacc of one (1) Dual Zone Module (DZMI. nine (9) initiating zones. Model CC may 6e expanded to a
<br /> maxi�wm of thirteen (13) initiating zones.
<br /> � Trim kits for semi-ilush mounting of each cabinet are available,
<br /> � AUXI LIARY SIGNAL CIRCUIT and are easily installed to provide a neat,tinished appearance.
<br />� The Auxiliary Signal Circuit Assembly (ASC) adds one (i) FACEPLATES
<br /> supervised Class "A" or "B" indicating cireuit to the system,
<br /> without tlie nced for an additional power supply. The module Faceplates for Zones 2 through 13 are ordered separately, as
<br /> snaps into the track area above the Common Control Assembly required. A blank faceplate (F4) is available to cover unused
<br /> (CCA-31,and is connected to the CCA3 using a plu�. space reserved tor tuture system expansion.
<br />
|