<br /> :OOI IVas�rg��n S�a�e Nonres�drninl Enp.py CW<Comp�ance Forms 1VerseC JW�:ro�
<br /> ' . Lighting - General Requirements . u�omae c ui ntro s, tener. E�Aerior
<br /> 1513 Lighting Controls. Lighling,includirg exempl lighting io lic�hting not intended for 24-Mur wnlinuous use shall be
<br /> automatically switched by timer,photocell,or a combination o(
<br /> SeUion 1512,shall compiy with this section.Where occupancy timer and photoceil.Automalic time swilches must also have
<br /> sensors are cited,Ihey shall have Ihe features listed in Seclion program back-up capabilities,which prevent the loss of
<br /> 1513.6.1.Where aulomatic lime switches are cited, Il,ey shall Pra�ram and time settings(or at least 70 hours,il power is
<br /> have Ihe(eatures tisled in SecGon 1513.E.2. interrupted.
<br /> 1513.1 Lowl Control and Access(bility.Each space, 1513.6 Automatfc Shut-OH Controls,Intodor. Office
<br /> enclosed by walls or ceiling-height paAitions,shall be provided buildings grealer Ihan 5,000 sq.tt.and all school classrooms
<br /> with liyhting conlrols located vrithin that space.The lighting shall bo equipped with separate aulomatic controls lo shut ofl
<br /> controts,whether one or more,shall be capablo of tuming off the Iighting durinc�uncewpied houc.Automatic coNrols may
<br /> all lights within lhe space.The conlmis shall be readily �an occupancy sensor,6me switch,or other device capable
<br /> accesside,al the point of enlry/ezit,lo personnel occupying or of aulomalically shuttin�off lighliny.
<br /> using the space. EXCEPTIONS:
<br /> EXCEPT10N5:The following Iighfing controis may be �, Areas Ihat must be continuously illuminated,or
<br /> cent2lized in remo�e localions: illuminated in a manner requiring manual
<br /> 1. Lighling conlrols for spaces wliich musl be used op��lion of the lighting.
<br /> as a whole. 2. Emerc�ency'ighting systems.
<br /> 2. Aulomalic conlrols. 3. SwitGiing for induslriai or manulacturirx�process
<br /> 3. Controls requinng trained operators. tacilities as may be required for produclion.
<br /> 4. Controls for safety hazarAs and security.
<br /> 15132 Area ConUols:The mawmum lightin�power Ihal may 1513.6.1 Occupancy Sonsors: pccupancy sensors shall be
<br /> be controlled from a single switch or auWmatic control shall not ����le of automalica9y tuming o(f all Ihe Iighls in an area,no
<br /> exceed Ihal which is provided by a twenty ampere circuit more lhan 30 minutes a(ter the area has been vac��ied.
<br /> loadecl to not more lhan eighty percenL A master control may 1513.6.2 Automatic Tirtw Switches:�ulomalic lirr�;switches
<br /> be inslalled previded lhe individual switches relain their shall have a minimum 7 day clock and be capable of being sel
<br /> a�pability to function independenUy.Circuit breakers may no� for 7 dif(erent day types per week and incorporate an automatic
<br /> be used as the sole means of switGiing. holiday"shut-otf'(eaWre,which Wms oll all loads for a1 Ieast
<br /> EXCEPTIONS: 24 hours and then resumes normally scheduled operations.
<br /> t. Induslriai or manufactunng process areas,as Automatic time switches shall also have program back-up
<br /> may be required for produdion. �pabilities,which prevenl Ihe loss of program and time
<br /> 2. Areas less than five sellings(or at least 10 hours,it power is interrupted.
<br /> percentoffootprintlor
<br /> (ootpnnts over 100,000 square feeL Aulomatic time switches shall incorporale an over-ride
<br /> 1513.3 Dayllght Zono Control:All dayliphted zones,as swilching device which:
<br /> defined in Chapler 2,both under overhead giazing and a) is readily accessible;
<br /> adjaceN to veAical glazinc�,shall be provided wiUi individual b) is located so that a person using the Jevice can see Ihe
<br /> r,ontrols,or daylight-or occupanbsensing aulomatic controls, lighls or the areas controlled by the switch,or so that the
<br /> which control the lights independent ut general area lightmg. area beirx�illuminated is annuncialed;and
<br /> Contiguous daylight zones adjacent lo vertical 9lazing are c) is manually operated;
<br /> allowed lo be controlled by a single wnlrolli�g device provided d) ailows the lic�htin�lo reinain on for no more than hvo hours �
<br /> Ihat Uiey do not inGude zones(adn�more than twv adjacent �+'��en an over-ride is initialed;and
<br /> cardinal onentations(i.e.north,east,south,wesl). Dayliyht e) controls an area not exceeding 5,000 square teet or 5
<br /> zones under overhead gtazin�more than 15 feet Irom Uie percent of(oolprinl for footprints over 100,000 square feel.
<br /> penrrr_ter shall bc controlled separately Irom daylight zones �+'�ichevcr is grealer.
<br /> adjacenl lo vedical glazing. 1573.7 Commissioning Roquiromonts: For lighling conlrols
<br /> EXCEPTION: which indude dayli�hl or occupant sensing au�omatic controls.
<br /> Dayiight spaces enclosed by walls or ceiling �u�omalic shut-olf controls,occupancy sensors,or automalic
<br /> hrighl partitions and containing 2 or fewer light lime swilches,ihe lighling conlrols shall be lested lo ensure
<br /> fizlures are ral required to have a separate swilch lor that conlrol devices,components,equipment and syslems arc
<br /> generai area iighting, calibrated,adjusted and operale in accordance with approved
<br /> 1513.4 Dis la ,Exhibition,and S cialt Li htin plans and sperifications.Sequences of operalion shall be
<br /> P Y P� Y 9 9 functionally testecl to ensure lhcy operale in accordance wiUi
<br /> Controls:AU display,exhibition,or speciaily lightinc�shall be approved plans and specificalions.A complete repod of tesl
<br /> controllcd independenlly of general area lighting. procedures and results shall be prepared and filed wilh the
<br /> o�mer.Drawing noles shall require commissioning in
<br /> acwrdance with this paragraph.