Laserfiche WebLink
. PROIER NAME: FLAKE BLDG TI <br /> IOB: N9•1624 <br /> Design of new Meuanin� iloor supporting a new oHice. <br /> Gravity Design <br /> Live load = 50 psf <br /> Dead load = 25 psf (iraming, light, hvac, etc.) <br /> Design rypical floor joist - maxir�um span = 12 ft <br /> 100 0 Ibl(1 <br /> � � <br /> y � y a ��� <br /> —� <br /> � 12.10' � <br /> 605 9.500 TJI 110 605 <br /> Load dura[ion =Floor Live, Cr.= 1.00 <br /> Live load =50.0,psf <br /> Dead load = 25D,psi <br /> Tnbutary width = 133,ft <br /> Beam/loist span,L = 12.10 ft <br /> Desfgn laads <br /> Max tolal moment,M= w l'/8= ]00.00�1210�'/A = 1830 ft-Ib <br /> Mex toti shear, V= w( /2 = 700.W�1210�/2 =605 Ib <br /> Max total reaction,R= w!/2 = 10000(12.10!/1 =605 Ib <br /> Beam design-9.500 Tll 110 <br /> Check Bendinq <br /> M' = M�capacity�C���C���=2380(1.00��1 00)=2380 ft-Ib <br /> M' = 2380 tt�lb >M = 1830.13 ft-Ib, RESUIT= PASS <br /> CheckShear <br /> CUSTOM DESIGN & ENGINEERING, IPiC. //_ �� \ <br /> November 11, 2013 �age 2 �/$ ) <br /> / <br />