Laserfiche WebLink
q <br /> , ._ _,.. , _ .��:,,,.-�,>«,�.� - <br /> � � � <br /> l <br /> � everett <br /> � <br /> � <br /> � Findings: <br /> � <br /> 1. Concentration levels are as shown on attachment. <br /> 2. Ventilation is as shown � attacMient. <br /> 3. Cooling coils are utilized in the installation. <br /> Itdn 3: Washington State Energy Code Table 4-16 limits the fnterior <br /> lighting power budget to 1.7 watts/sf plus 2%/ft of ceilirx� <br /> height exceeding 20 feet. <br /> The process of tubing fabrication requires 80 foot candle based on <br /> the camplexity of work. <br /> The ceiling height is 24 feet and 36 feet. <br /> Actlon: <br /> � � Accept the calculations requiring 2.5 to 3 �atts per sf based on <br /> ` Illuminating Engineering Society unit power density. <br /> ( Findings: <br /> 1. Ceiling height is required because of material lengths. <br /> , 2. Lighting level is required because af work process. <br /> ; <br /> I (5379H) <br /> � <br /> � � <br /> � <br /> � <br /> � <br /> � <br /> 1 � <br /> ( 2 � <br /> � � <br /> � I <br /> , <br />