Laserfiche WebLink
( C <br /> Ltr. C0804-007 <br /> April 28. 2008 <br /> Page 2 <br /> 9. Specify scale of the section drawing on Shect A6. Show dimensions that were left off <br /> of section. <br /> !0.Provide detail of"Gutter" construction. Show how gutter is drain�. ' <br /> 11.The maximum sone rating for the whole house fan shall be 1.5 or less, not 15 as shown <br /> on the plans. �i <br /> 12.Pravide the offset dimensions of the second floor walls from the first floor walls. <br /> Show in plan view and sections. <br /> 13.Provide minimum 36" landing at the top of the stairs per Section R311.5.4 IRC. <br /> 14.Provide minimum 18" x 24" crawl space access. Show on plans. <br /> 15.Cross reference building section to structural details. Building section should reflect <br /> the actual construction proposed. <br /> 16.The foundation plan references detail N2 on Sheet S4, detail M2 on Sheet S4 references <br /> the foundation plan; neither sheet shows plate size, anchor bolt size or spaGing, or the <br /> required plate washers. Please clarify (See b'15 above). <br /> Please prep are a response letter showing where each item tn this correction <br /> letter is addressed on the plan set. <br /> Upon resubmittal of the drawings, your application will be given priority and plan review wiU <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure i <br /> that the proposed structure will be constructed in compliance with all adopted codes. <br /> Sincerely, � <br /> _����f�..L1—�' <br /> � <br /> Jeff Hei an <br /> Development Technician <br /> �� <br /> UI!I)1/PINCI(MSf/lI1F.IW�NKD10�-0D7 R�71 CIIF37NVT Tfl <br />