. , <br /> b) Exurior concrete wall partial heig6t with wood framed cripple wall <br /> c) Exterior wncrete wall fuil height <br /> d) Interior partidons <br /> Ail cross sections shall be of sufficient detail to show construcdon and energy code <br /> compliance. <br /> 5. Provide tempered glass in required hszardous locations as defined in Section 2406 UBC. <br /> Show on plaas. <br /> 6. Provide amoke detectors in aU sleeping rooms and in the corridor or area giving access to <br /> each separate sleeping area. <br /> 7. Provide minimum SO cfm fan in bathroom. <br /> 8. The walls and soffit of useable space under stairs is required to be S/8" type `X' GWB. <br /> Show on plans. • <br /> 9. Provide minimum 36" lsnding at all entrance/exits not more than 8" below the finished . <br /> floor. <br /> 10. Submit nquested engineers letter/report for pile placement. (Inspection report dated <br /> 9/10/96, 9/6/96 and 9/5/96.) <br /> Prepare a response letter showing where each item in this cortection letter is addressed on the plm <br /> set. <br /> Upon rcsubmittal of the drawings, your application will be given priority and plan rcview will <br /> rccommence. <br /> All required submittals sMall be of sufficient detail and contain sufficient infocmation to engure that <br /> the proposed ewcture will be constcucted in compliance with all adopted cades. <br /> Sincerely, <br /> �� <br /> J ilman <br /> velopment Technician <br /> l�lo re� �s�d pbns were p �ov;dPc�� <br /> GHo� �l,e vaic�ec� appl�cRfi'vv� aKoe <br /> �, le �-� �P��� 7' C SL3oZ WEr �. <br /> Seh�- �v /2�co�ru{S ?a�ai� , 20�/ <br /> DEDI/PLNCKMSTR/HEILMAN/5129 CHINOOKDR <br />