Laserfiche WebLink
ARCHITECTURAL PLANS REVIEW COMMENTS <br /> Richerd M. Swanson <br /> Phone:(360)705-6782 <br /> Fax: (360)705-6654 <br /> Net: RMS0303Qhub.doh.wa.gov <br /> FACILITY : Providence General INedicsl Center-Colby Campus <br /> PROJECT: Telenetry <br /> CRSN : 97-0022-4912-001 <br /> DATE : May 6, 1997 <br /> 1. Provide mechanical plans showing any and all plumbing and HVAC revisions. WAC 246- <br /> 318-510(2)(c) <br /> 2. Provide electricel plans showing circuitry and which are critical emergency oudets. WAC <br /> 246-318-510(2)(c) <br /> 3. Identify what the piece of equipment is which is labeled "MED STATION"in Nurse Statlon <br /> 09. WAC 246-318-510(2)(b)&(c) <br /> 4. Identify what is meant by the initiais "H.U.C.". <br /> 5. Clean Utility Room 10 shall be a room separated from all other functions by full height well <br /> partitions on all sides end ail openings provided with window or door assembiies. WAC 246- <br /> 318-010, Definition oi a"Room". <br /> 6. Verify all the doors to Clean Utility 10 are 20-minute rated assemblies with closers. WAC <br /> 246-318-540(2), Sec. 1005.8.1, Uniform Building Code <br /> END OF REVIEW COMMENTS <br /> i <br />