Laserfiche WebLink
1 <br /> MECHANICAL/ELECTRICAL PLANS REVIEW COMMENTS <br /> MARI EICHNER <br /> Phone: (360)705-6783 <br /> Fax: (380)705-6854 <br /> Net: MBE0303�hub.doh.wa.gov <br /> FACILITY: Providence General Medical Center-Colby Campus <br /> PROJECT: Teiemetry <br /> C RSM: 97-0022-4912-003 <br /> DATE: September 29, 1997 <br /> ELECTRICAL PLAN REVIEW <br /> . Please verify ali electrical receptacle outlets located within five feet of a sink, lavatory. toilet, <br /> � and bathing facilities are protected by a ground fault circuit intertupter. WAC 246-318- <br /> 540(5)(a)(i) and WAC 246-31 B-540 Table 5 Note(B) <br /> •�•}�•++titifi•+a+ti� NOTAPPROVED <•�titi+•}�?�}fi4•'r <br />