Laserfiche WebLink
� <br /> • .� <br /> � � i <br /> 9 E <br /> Y �i ' g <br /> E <br /> � u' < z <br /> C2 18 � Provide a reduced pressure backflow assembly on thc water service to the pop <br /> machine. WAC 246-320-540(4)(a),WAC 246-215-120(4), and WAC 246-290-490 <br /> Approved 11/15/02-See M6.1 riser 315. <br /> C2 l9 � An exemption will be required to locate a water closet within the ICU patient room. <br /> FVAC 246-320-065, and WAC 246-320-725(2)(c) <br /> Approved Y1/IS/02-Water closefs are located in toilets. <br /> C2 20 � Enclose the nourishment room. WAC 246-320-535(6) <br /> Approved l V15/02- Nourishment funcHon is in side rooms C215 and B341. <br /> C2 21 � Provide tamperproof receptacles in Waiting room P007 in accordance with <br /> WAC 246-320-405(9)(e)(ii). <br /> Approved 1ll2L02-Based on drawings received 11/Ol/02,which show locstlons <br /> of required tamperproof receptacles. <br /> C2 22 � Ice machines shall have appropriate backflow protection. Air-cooled ice machines <br /> shall have an air sepazation or air-gap on the drain line. Water-cooled ice machines <br /> shall have a reduced pressure backflow assembly on the potable water lines and an <br /> air gap separation on both drain lines. WAC 246-290-490(2)(b) i <br /> Approved 11/15/02-See M6.1. <br /> C2 24 � Provide fire smoke/d�mpers at penetrations of the l-hour occupancy sepazation that <br /> defines the boundaries of the suite. WAC 246-320-405 (6), Section 713 (0, Unifortn <br /> Building Code, and Section 713.11, Unifortn Building Code.The wall shall be <br /> constructed per Section 3023(4), Uniform Building Cale with all openings <br /> protected by a fire assembly having a one-hour rating fire protection rating. <br /> Approved 11/21/02-Based on�lrawings ceceived I1/Ol/02,which show <br /> fire/smoke dampers at all required locations. <br /> C2 25 � Suites shall not exit through adjoining suite. Section 1007.5.9, Uniform Building <br /> Code amendments <br /> Approved 11/25/02-Norlh half of Wing 3C is a suite tl�at exits to rated <br /> corridors at two locations. South half of Wing 3C is N��T a suite, but has ell <br /> patient rooms opening to a rated corridor. <br /> C2 26 0 Provide a detail of the dialysis box. <br /> Approved 11/15/02 -See M6.2 <br /> Pagc 7 0( I I Plan Review Comments For Project#6345 <br /> Review Key: A=Archi�cci F=Fire&Life Safe�y S=Sanitarian M=Mechanical/8leclrical C=Conferrna NWe <br /> �1 <br />