P!!BL/C N/O/�ACS <br /> ������ <br /> ADMINISTRATIVE ACTION <br /> DATE: July 14, 1993 <br /> SUBIECT: Everett High School Main Building <br /> ACTION: Partial enclosure of the north and south exit stairs will be provided . <br /> on all levels. 1'he enciosure will consist of 1-hour rated walis and <br /> doors on the north side of the south stair and on the south side of the <br /> north stair. All other doors to classrooms, etc., will be 20 minute <br /> rated. <br /> Enclosure of the main entrance stair is not required. <br /> FINDINGS: ' The occupant load of the third level excexds 500 and requires 3 <br /> exits. <br /> ' Two (2) exits from the third level are existing. <br /> ' Section 3309 requires stair enclosures. <br /> ' The existing stairs are open. <br /> ' The occupant load and use of the building are not changing <br /> significantly. <br /> • It is technicall� infeasible to add another exit to the third level <br /> due to the historic nature and construction of the existing <br /> building. <br /> ' An automatic fire sprinkler system is being added to the building. <br /> ' The existing construction is being repaired to provide a Type III <br /> 1-Hour building and being seismically retrofitted. <br /> ' The existing building was built prior to the adoption of building <br /> codes and has remained significantly unchanged for over 85 <br /> years. <br /> - ��� P <br /> �; <br /> Y , BUI DING OFFICIAL <br /> na:;��.a�,.at cvnu9�) <br /> cc: Richard Heindel, Dykeman Architects <br /> Mike Gunn, Everett School District <br /> CITY OF EV[RETT•3200 Cedar Street • Everett, WP 38201 • (206) 259-8800 • Fax (206) 259-8856 ';-` <br />