Laserfiche WebLink
5 <br /> EVALUATION OF ATI SUBMITTAL FOR BRUSH AERATORS <br /> BID No. 2004-696 <br /> Item 1: Electric Motor <br /> The Motor proposed by Ati does not meet the specification for several reasons: <br /> • ATI proposes a Motor Service Factor of 1.15. The specification requires a Service Factor <br /> of 1.25. <br /> • ATI proposes class F insulation and no mention of slot caps or liners, with spray <br /> enamel coatings. The specification requires class H insulation with silicone slot caps <br /> and liners, and epoxy coated windings. <br /> • Ati proposes a TE enclosure. The specification requires a TEFC enclosure. <br /> Item 2: Gear Reducers <br /> The Gear Reducer proposed by Ati does not meet the specification: <br /> • ATI proposes a standard Lip Seal for the Gearbox. The specification requires either an Inpro <br /> or Protec Seal. <br /> Item 3: Horizontal Rotor Assembly <br /> The Rotor Assembly proposed by ATi does not meet the specifications for several reasons: <br /> • ATi uses a Schedule 10 Torque Tube. The specification requires a Schedule 40 Torque <br /> Tube. <br /> • The Rotor Drive and Tail Shaft for ATi Aerators are 304 Stainless Steel. The specification <br /> requires 316 Stainless Steel. <br /> • The Rotor Drive and Tail Shaft for ATi Aerators are welded in place (I). The specification <br /> requires the Rotor Drive and Tail Shaft be bolted in place using 316 Stainless Steel <br /> hardware. <br /> • The Rotor for ATi Aerators is Hot-Dipped Galvanized. The specification requires Stainless <br /> Steel or Powder Coating. <br /> Item 4: Main Frame <br /> The Main Frame proposed by ATi does not meet the specification: <br /> • The ATi Main Frame is Hot-Dipped Galvanized. The specification requires Stainless Steel or <br /> Powder Coating. <br /> Item 5 Mooring Assembly <br /> The Mooring Assembly proposed by ATi does not meet the specification: <br /> • The ATi Mooring Assembly is Hot-Dipped Galvanized. The specification requires Stainless <br /> Steel or Powder Coating. <br /> Item 6 Housing and Splash Guard <br /> The Housing and Splash Guard proposed by ATi does not meet the specification: <br />