<br /> Lighting -General Requirements 1571.6 Automelic Shul-0H Controlc,ineeNor:euiiainps
<br /> �51J Lighting Controls. Lighling,Inclutling exempt lighting 9�eater than 5,000 sq.rt.antl all school classrooms shall Ge
<br /> in Seclion 1512,shall com I with Ihis.5eclion.Where eQuippetl wl�h saparate automatic controls to shut oR ihe
<br /> P Y lighting during unoccupietl zours.Wilhin these buildings,all
<br /> occupancy se�sors are cited,they shall have the features oKce areas less ihan 300 tt enclosed by walls or ceiling-
<br /> lisled in Section'1513.6.1.Where automalic time switches are heighl partitions,and all meetln{7 antl conterence rooms,and
<br /> cited,they shall have the features lisled in Seqlon 7513.6.2. all school classrooms,shall be�equipped with oaupancy
<br /> '1513.1 Local Control and Accesslbility: Each space, sensors that comply Secfion 75'13.6.L For other spaces,
<br /> encloscu by walls or ceilinq-helght partitions,shall be provitle� au�omalic conirols may be an occupan�y sensor,lime switch,
<br /> with i„�,h�,ng conlrols located wlthin that space.The lighting or other davice caaable ot automatically shutting ort lighling.
<br /> controls,whelher one or more,shall be capable of tuming oH EXCEPTIONS:
<br /> all lighls within ihe space.The wntro�s shall be reatllly 1, qreas ihat must be continuously Illuminaled(e.g.,
<br /> accessible,at the point of entry/exit,to personnel occupying or 24-hour convenience stores),or illumfnated in a
<br /> using lhe space. manner reyWring manual operetion of the
<br /> EXCEPTIONS:The Tollowing IlBhting conirols may be Ilghting.
<br /> cen�ralized in remote Iocations: 2. Emergency ligh�ing systems.
<br /> 1. Lighlin6 controls for spaces which must br used 3. Switching for Industrial or manufacluring process
<br /> as a whole. facllilies es may be required Tor producllon.
<br /> 2. Automatic controls. 4, Hospitals and laboratory spaces.
<br /> 3. Conlrols requiring l�ainetl ope�abrs. 5. Areas In which metlical o�denlal tasks are
<br /> 4. ConVols for safety hazards antl security. peNormetl are exempt Imm the occupanty
<br /> 1573.2 Area ConVols:The ma�dmum Ilghting power thal may sensor requlrement.
<br /> be conirolletl irom a sin�le switch or automalfc coNmi shall not �513.6A Occupancy Sensors:Occupancy sensore shall be
<br /> exceed Ihat which is provitletl by a twenty empere circuit �Pable ot aulomalically tuming ott all the lights In an area,no
<br /> loatled to not more ihan eighty porcenL A master conirol may more ihan 30 minutes aIIer the area has been vacatetl. Light
<br /> be Installed provided ihe Intlividual switches retain thelr fixtures controlled by occupancy sensors shall have a wall-
<br /> rapablllty to tunction Independently.Clrwit breakers may not mounted,manual switch capable of tuming ofl lighis when the
<br /> bo usetl as ihe sole means of swltchina. space Is ocwpletl.
<br /> EXCEPTIONS: �5�3.6.2 Automatic Time Swltches:Aulomatic time SwilUieS
<br /> 1. Intlustriai or manufacturing process areas,as shall have a minimum 7 tlay Gock and be capable ot being set
<br /> may he reqWretl Por pmtluction. {or 7 dirterent tlay types per week and inwrporate an
<br /> 2. Areas Iess than fivo percent of foolpdnt for automatit holiday"shut•otr'IeaWre,which tums oft all loatls for
<br /> foolprints ovr,r 100,000 squaro foet. at least 24 hours and ihen resumes normally scheduletl
<br /> 1513.3 Dayllght Zone Control:All tlayllghted zones,as operations.Automatic time switches shall also have program
<br /> tlefined In Chapter 2,both under overhead glazine and badc-up capabililies,which prevent the loss of program and
<br /> adjacent to vertical glazing,shall be provlded with Intlividual time setlings for at least 10 hours,if power is inlerruptetl.
<br /> contmis,or daylighbor occupant-sensing aulomalic conlrols, Automalic time switches shall incorporate an over-ride
<br /> which control tne Ilghts independent of general area Ilghling. swltching device which:
<br /> Conliguous tlaylight zones adjacent lo venlcal gtazing are a) Is readily accessl6le;
<br /> allowed to be controlletl by a aingle controlling device provided b) is iocatetl so that a person using Ihe devlce can see the
<br /> �hat Ihey do not InUude zonas tadng more than iwo atlJacent lighls or tha areas conlrolled by ihe svritch,or so ihat the
<br /> cardinal orientalions Q.e,noRh,east,south,west). Daylight area bein�Illuminatetl is annunciatetl:and
<br /> zones under overheatl glazing more than 15 feet from the c) Is manually operated;
<br /> perimeler shall be controlled separalely 1rom tlaylight zones tl) allows the lighting to remain on lor no more than two hours
<br /> atlJacenl to vertical glazing. when an over-ride Is iniliated;and
<br /> EXCEPTIOt.: e) contmis an area not exceetling 5,000 square leet or 5
<br /> Daylight spaces enGosed by walls or ceiling percent oi footprint for(ootprints over 100,000 square 1eet,
<br /> height parti�ions and contalning 2 or tewer Iight whichever Is grealer.
<br /> fix�ures are not requlred�o have a separate switch/or �5�3.7 Commissloning RaqulremenLS: For ligh�ing conirols
<br /> general area lightlng. ���h Indude dayligM or ocwpanl sensing automatic conirols,
<br /> 15�3.4 Dlsplay, Exhi6ltion,and Speclalty Ll�hting auloma�ic shut-ott conlrols,occupancy sensors,or automatic
<br /> Controls:All display,cxhibitlon,or specially lighting shall be time svrilches,the Iighlin0 controls shall be tesletl to ensure
<br /> conirolled Intlepentlontly of general area IlBhting. that control devices,components,equipment and systems are
<br /> 7513.5 AutomaUc ShuFOR Controls,Extedor.EMerior calib2ted.adjusted anA operele in accortlance wilh appmvetl
<br /> Iighting not Intended for 24hour continuoue use shall be plans and specificalions. Sequences of operation shall be
<br /> automalically switched by timer,photocell,or a combination of funclionally testetl to ensure lhey operale In accordance wilh
<br /> timer and photocell.Automalic time switches must also have approved plans and specifications.A compie�e report of test
<br /> program back-up capaUillUes,which prevenl�he loss of procedures and resWts shall be prepared and Gled with tha
<br /> program and time so�tings tor at least 10 hours,It power is owner.Drawing noles shall require commissioning In
<br /> Interruptetl. accordance with tlils paragraph.