2001)�'�shington Stete Nonrosidential EnerRy Code Ca��liance Form
<br />Lighting - General Requlrementa
<br />1613 Llghting Cantrola. Llghting, includirq exempt Iqhting In
<br />SecFon 1512, shtill wmpiy with this sedlon. Where occnpency
<br />s� �sors are ciled, they sheli have the feetures listed in Sectlon
<br />15+ :.6.1. Where automatic time sv+itrhes are cited, they sheli
<br />heNn the teatures IBted In Sepion 1513.82.
<br />1673.1 Lxal COMroI and A:cesuibility: Each 5paca,
<br />enGosed by walls or celling-helght pahitinns, shall be povided
<br />w8h Iightlng controLv located within that space. 7he lighling
<br />controls, whelher one or more, shall be c&pable of tuming ofl
<br />ell iights within the space. Tho cantrols shali be reatlily
<br />accessible, et the polnl ot enlry/exit, ro persannel occupying or
<br />using tha spece,
<br />EXCEPTIONS: The following lighting controls may be
<br />centralized (n mmote IocaUons:
<br />1. Ligliting controls for spaces which must be used
<br />as e whole.
<br />2. Autometiccontrols.
<br />3. CoMrols requiring trained operators.
<br />4. ConUols for safety hezerds and security.
<br />1613.2 Area Controls: The meximum lighting power that may
<br />be corri�otled hnm a single swNch ar eutomalic conirol shall not
<br />exceed ihat which is proNded by a trrenty ampere Grcuit
<br />loaded to not more than eighty percent. A master control may
<br />be instelled provided the indivklua� swAches retain their
<br />capabiiiry to fundion Independently. Circuit breakers mey not
<br />be used as lhe soie means of swltchin0•
<br />EXCEPT10N3:
<br />1. Industriel ormanutaduring pmcess arees, es
<br />may be requi:ed for produIXion.
<br />2. Areas Iess then five percenl of Motprint for
<br />footprints over 100,000 squere feel.
<br />1673.3 DeyligM Zone CoMrol: All daylighted zones, as
<br />defined In Chapter2, 6oth underoverheed �lazing and
<br />edJecent to veAical glazing, shail be pmvlded with individual
<br />controls, or daylipht•or occupant-sensing aulamatic conlrols,
<br />which control lhe Iights independenl ofgenerel area Iighting.
<br />Contiguous deylight zones adjacenl to wAical glezing are
<br />allowed to be canimlled by a single controlling device proviUed
<br />ihet they do nol inGude zones facing more than two adjacent
<br />cardinai orientations (i.e. north, east, south, west). Daylight
<br />zones underoverhead giazin{� more then 15 (eel from Ihe
<br />perimeter shall be canlrolled seperalely from dayllght zones
<br />adjecent to �eAical glazing.
<br />EXCEPTION:
<br />Deylight spaces enclased by walls or ceiling
<br />heght paRitions end conta(ning 2 or tewer Iight
<br />fiAures are not required to have a separale switch for
<br />(�enerel area lighting.
<br />1b13A Di:apiay, Exhibkiun, and 3peclalty LigMing
<br />Controls: All display, ek�ibition, or specialty lighting shali be
<br />controlled Ind=pendenliy of yoneral area lighting.
<br />1b1�.6 Automatic Shut-0ff Canrols, Exterior: E�derior
<br />lit;hting not intended for 24•haurconGnuous use �hell be
<br />automatically switched by timer, photoce�l, or a combination ol
<br />timer and pho�ocell. Aulomatb time swRchas must also heve
<br />propram back-up capabildies, which prevent the loss ot
<br />prugrem and timo settings for ef leasl 10 hours, if pnwer f�
<br />Inlertupted.
<br />1613.6 Automet=.c Shut-OPf Cantrols, ;Mada: Ofl'ice
<br />buildings greater lhan S,OUD sq. fl. and all school classroums
<br />shell be equlpped with separate automeUc controls to shu; otl
<br />t�e Nghting during unoccup:ed hours. Automadc oontmts may
<br />be an occupency sensor, time swllch, or other devi;e capable
<br />af sciomalicnlly shutling off Ightlna.
<br />EXCEPT10N5:
<br />1. Areas thnt must be continuously Illuminatod, or
<br />Illumtneled In a manner requiring manuel
<br />operation of the Ii3hling.
<br />2. Emergency Iighting systems.
<br />3. Switching tor induslrial or manufedurtng process
<br />facilities as mey be requlred for pmducibn.
<br />1613.6.1 OccupancySenson: Oaupancy sensors shall be
<br />capable oT automeSic�lly tuming ott alt the Iights In en area, no
<br />more than 30 minules aRerthe area has been vaceted.
<br />1619.8,2 Automatic Time Switches: Automntic time swRches
<br />shall have e minimum 7 dey ckck end be capable of being set
<br />tor 7 diflerent dey typas per week and incorporate an automa0s
<br />bolidey'shu4ofi" feature, which tums oR ell bads tor at !^ast
<br />24 hours and then re�umes nortnatly scheduied operetions.
<br />Automatic time switches shell also have program back-up
<br />capabilities, which prevenl lhe loss of progrem end lime
<br />settings for at least 10 hours, if power is fntenupted.
<br />Automatb time swilches shali Incorporate an over-ride
<br />swttching device which:
<br />e) is readily eccessiWe;
<br />b) is lacated so Ihat a person using the devlce can see Na
<br />Ilghls or the eieas conimlled by the swilch, or so ihal the
<br />area beinB �Iluminated is ennuncia�ed; and
<br />c) Is manually operated;
<br />a) allows the Iighling to remain on for no rtrore then two hours
<br />when an overvride is (nitialetl; and
<br />e) conlrols an area not exceedinp 5,000 square fcet or 5
<br />percent of footprint for tootprims over 100,000 square Ieet,
<br />whichever is greater.
<br />1613.7 Commlasioning Requirementa: For lighting controls
<br />wh(ch inciude daylight oroccupant sensing aulomatic cantrols,
<br />automatic shut-ofl ccntrols. ;ccunancy s?r�sors, or automatic
<br />tlme switches, the lighting ccntrols shall be tested to ensure
<br />that contiol devices, compo�ienls, equipment and systems are
<br />calibra(ed, adjusted and oFerete in accaNance wflh approved
<br />plans and speGfications. Sequences of operallon shall be
<br />fundionally tested to ensare they operate in accordance with
<br />approved plans and so�.ufications. A complete repoh o( tesl
<br />procedures and rasutts shall be propared and fled wilh Ihe
<br />owner. Drawing notes shall require commissioning in
<br />accordance wilh this paragraph.