:NG/NEElt//6'G / Pl1BL/C 5El�fi/CE5 OEPA?TiNEJYT <br />January 2b, 2009 <br />Russcll Crouch <br />Gnfinity Lnginccring <br />9019 Ovcrlaok Boulevurd, Suitc G4 <br />[3renhvood,'tennesscc 37027 <br />SUBJECT: Davita Dialysis — Cvcrctt, Washington <br />Pcrmit L0901-020 <br />i� 30 � �'-et� n�e � �� <br />Dcar Mr. Crouch, <br />In ordcr to flcilitate cicctrical plan rcvicw of this project, plcasc address thc following: <br />1. '�e emergency side of the transfer switch requires overcurrent protcction or <br />Pancls A, C, and D rcquire main brcakcrs. <br />2. Providc a drawing showing available fault currcnts and sliort circuit intcrrupting <br />ratings of equipmcnL [nclude fault current analysis. <br />3. Providc manufacturcr's installation instructions for thc hemodialysis units diat <br />will bc installcd. <br />4. Receptacics that scrvc equipment such as, Uut not limitcd to, rcceptacles for <br />dialysis machines or computers, are classified as equipment loads and must bc <br />accorded a demand factor of 100"/0. <br />5. Lighting cxpected to be on more than threc hours is a continuous load and must <br />bc accorded a demand factar of 125%. <br />If you havc any qucstions, plcasc call mc at (425) 257-5310. Thanks. <br />Sinccrcly, <br />_ ���,'� �� I � � <br />Tim Alaniz / <br />Glectricallnspcctor � <br />S:ikcollisi��Al;mirJllovila Dialysis (I:OJOI-020) <br />CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 •(425) 257-8800 • Fax (425) 257-8856 <br />