2009 Washington State Egargy Code Compliance Form for Nonresidential
<br />Residential
<br />0 Warehouse or Parking Garage * Other
<br />Zualifieation Checklist Lighting 2 Check if 95% or more of fixtures comply with 1,2 or 3 and restate ballasted.
<br />Note: it occupancy type is *Other* and future Fixtures: 1. Fluorescent fixtures with a) 1 or 2 two lamps, b) reflector or lowers,
<br />answer is checked, the number or futures in (Section c) 5-60 watt T-1, T-2, T4, T-5, T-8, or CFL lamps, and d) hard -wired electronic
<br />the space is not limited by Code. Clearly 1521) dimming ballasts. Strew -in CFL fixtures and tacking lighting do not qualify.
<br />indicate these spices on plant:. Knot
<br />qualified, do LPA Calculations. 2. Metal Halide with a) reflector b) ceramic MH lamps <=150w c) electronic ballasts
<br />3. LED'
<br />TABLE 15-1 Unit Lighting Power Allowance
<br />r
<br />LPA Wlft
<br />Use
<br />LPA Wlft Wl
<br />0.85
<br />Use
<br />U
<br />Office buildings, officeladminislrativeoreas in facilities
<br />0.91
<br />Automotive facility
<br />of other use types (including but not limited to schools,
<br />hospitals, institutions, museums, banks, churches)'
<br />Convention center
<br />1.10
<br />1.10
<br />Parkin ara as
<br />Penitenlia and other Grou I-3 Occu ancies
<br />0.20
<br />0.90
<br />Courthouse
<br />1.20
<br />Police and fire stations
<br />0.90
<br />Cafeterias, fast food establishments ,
<br />seslaurantslbarss
<br />0
<br />Post office
<br />1.00
<br />Dormilo f
<br />1.85 00
<br />Retail ,retail banking, mall concourses, wholesale
<br />1.33
<br />Drmit
<br />stares allot rack shel4
<br />0.95
<br />School buildings (Group E Occupancy only), school
<br />1.00
<br />Exercise center
<br />classrooms, day care centers
<br />Gymnasia, asse ribly spaces
<br />0.95
<br />Theater, motion picture
<br />0.97
<br />1.25
<br />Health care clinic
<br />1.00
<br />Theater. performing arts
<br />0.80
<br />Hospital, nursing homes, and other Group 1.1 and
<br />1.20
<br />Transportation
<br />1-2 Decu ancies
<br />1.00
<br />Warehouses
<br />0.50
<br />Holellmotel
<br />Laboratory spaces (all spaces not classified
<br />1.62
<br />Workshops
<br />120
<br />"laboratory' shall meet office and other appropriate
<br />categories)
<br />1.20
<br />Laundries
<br />1.20
<br />plans Submitted for Common Areas Onl
<br />Libraries1.10
<br />1.20
<br />Main floor building lobbies ezce t mall concourses
<br />Manufacturing Tacilay
<br />1.00
<br />Common areas, corridors, toilet facilities and
<br />washrooms elevator lobbies
<br />0.80
<br />Museum
<br />Footnotes for Table 15-1
<br />1) In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use is not mentioned
<br />specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most
<br />comparable use specified in the table. See Section 1512 for exempt areas.
<br />2) The watts per square foot may be increased, by 2% per fool of ceiling height above 20 feet, unless specifically directed otherwise by
<br />subsequent footnotes.
<br />3) Watts per square fool of room may be increased by 2% per foot of ceiling height above 12 feel.
<br />4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
<br />5) Watts per square fool of room may be increased by 2% per fool of ceiling height above 9 feet.
<br />6) Reserved.
<br />7) For conference rooms and offices less than 150f? with full height partitions, a Unit Lighting Power Allowance of 1.1 wlfl may be used.
<br />8) Reserved.
<br />9) For indoor sport tournament courts with adjacent spectator seating over 5,000, the Unit Lighting Power Allowance for the court area is
<br />2.60 Wife. to
<br />10) Displwallsaor at least three-quwindow arter-height partitions (transparenton Installed within 2 feet of the ior opaque) and lighrovided that ting fhe or free-standing y window Id splay where rthelightinig moves y
<br />with the display are exempt.
<br />An additional lighting power allowance is allowed for merchandise display luminaires installed in retail sales areas that are specifically
<br />designed and directed to highlight merchandise. The following additional wattages apply:
<br />t. 0.6 wafts per square foot of sales floor area not listed in items it and !it below;
<br />ii. 1.4 watts per square foot of furniture, clothing, cosmetics or artwork floor area; or
<br />iii. 2.5 watts per square foot of jewelry, crystal or china floor area. The specified floor area for items I, it, or A above, and the adjoining circulation paths shall be identified and specified on building plans.
<br />Calculate the additional power allowance by multiplying the above LPDs by the sales floor area for each department excluding major
<br />circulation paths. The total additional lighting power allowance is the sum of allowances for sales categories I, it, or ill plus an additional
<br />1,000 watts for each separate tenant larger than 250 square feet in area.
<br />The additional wattage is allowed only d the merchandise display luminaires comply with all of the following:
<br />(at I :zaced on veiling -mounted track or directly on or recessed into the ceiling itself (not on the wall).
<br />(b) Adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two
<br />points of track attachment).
<br />This additional lighting power is allowed only if the lighting is actually installed and automatically controlled, separately from the general
<br />lighting, to be turned off during nonbusiness hours. This additional power shall be used only for the specified luminaires and shall not be
<br />used for any other purpose.
<br />This additional lighting power is allowed only If the lighting is actually installed.
<br />11\ om,ria<a thef o (Im,r oleo indirefinn nr4 lnrofinn enA hoinht ie u,hmieed the enuvs (nnlen< (nr o wnrnhnuen mm, he dulnnd Inr