Laserfiche WebLink
Conuuent 3. I3uilding cross section indication floodcciling, roof/ceiling and wall constniction <br />adj�cent to or penetrated by Type 1 hood, erease duct and exhaust. <br />a. Indicates support of Type [ hood to swcturc. <br />Rcsponsc: Detail 6 on b1-1.1 shows the roof curb and angle iron frame openin�. Sce <br />detail 2 on drawing A-8 for support of hood. <br />b.and c. Grease duct systems and exhausts equipment: 3 iuch cicarance to �rypsum <br />wallboard/metal stud wall or I R cicannce to wood construction (altcrnatc reduction <br />melhods per Table 308.( 200C Internatianal Mechanical Code). All type I lioods are <br />required to have 18 inch clearance from combustible �call construction, per IMC 507.9, <br />or the wall behinJ the Type I hood should bc identitied as combuslible wood walls nre <br />summarized on the attnchcd information shcet, ��s excerpted Gom thc IMC. <br />Rcsponsc: The exhaust ductwork li•ori thc Typc [ hood is to be wr�pped ���ith a one hour <br />firc rcsistant duct �vrap per thc altcrnatc reduction method listed in comment 3c. Detail <br />#( on sheet M-I.1 lists this reyuirement. �Ve have also adcled a note stating this <br />rcquirement to the plan on sheel M-1.0. <br />d. Indicate clearance to cooking equipment. llood size a:�d overhang dimensiais <br />(vertical and horizontal) shouid be located on U:e drawings per IMC sections 507.1 I and <br />507.12. <br />Respm�se: Clearances to cooking cquipment can be (ound on equipment plan dra«�ing <br />A-4 (horizontal dimensions) and elevations drawings (vcrticnl dimensions) det�ils 7/A-G <br />and 8/A-G. The equipment schedule on drawing A-�4 list the Type 1 hood as item number <br />35 lialton hoad with the sizc in the remarks coluum at 54" X 72". <br />Commenl 4. lnterior elevation should indicate the extent otstainless stcel wnll finish extending <br />18 inches past 7'ype I hood (and rnnge) in all dircctions. Smooth cleanable m�teriai finishes and <br />thc required eatension Gom the Type 1 hood should be indicated on thc drawings, per IMC <br />Section 507.9. <br />Rcsponsc: Scc interior clevations 7/r\-( and 8/A-6. <br />Cummcnt 5. A hingc should be indicated on the dra�ving at the upblast fan for Typc 1 houd, per <br />IMC 506.53, with flexiblc, wwtheiproof cable. <br />Responsr. A hingcd base has becn added to the specification ott the fan schedule on shcet M-1.0 <br />Cmnment C. l�loor plan of equipmcnt, �vall constn�ction and materials should bc located and <br />identiticd on the drawines, per the wmments on the building permit submittal 130712-042. <br />Rcspanse: See cqui;•,ment Plan A-4 and w�ll section rypes on drawing A-3. <br />Application K0802-003 <br />Comment I. The tire suppressiun pennit K0802-003 should indicate that thc suppression <br />systcm �vill activate the building alarm system required by [he Tenant I�uprovemeut Building <br />Pennit I30712-042. <br />Responsc: Fire suppression system det�ils, wiring diagram, and (irc alarm criteria is shown on <br />shcet r-2.0. <br />ArCor, inc. � 3 <br />831 lamcs Street, Syracuse, New 1'ork 13203 <br />Phonr.(31i)233-1300 cst.11l P:u:(315)233-1314 <br />���v�v.ancorinc.com <br />