March 27, Z012 <br />)ames Palda <br />18100 Von Karman, #500 <br />Irvine, CA 92612 <br />RE: Owner: SteadfasL Commercial Property <br />Job Address: 1902 SE [verett Mall Way ll's 375, 330 &�SS <br />Plan Chedc No: [310J_03-014 through O16 <br />Dear Mr. Palda: <br />ii� res�onse to your applic�ition for � construction permil, yow- plans have L�een examined and <br />you are advised that Che issuance of a permit is being withheld for the reasons listed belova. <br />These �omments address building issues only. Additional revisions, or addiLions, may be <br />required by other departmenLs (such as Utilities, Planning or Fire). All references refer to the <br />2009 Inlernational Building Code, as amended by tlie Slate of Washington and adopted by the <br />City of Everett and the Washington State Energy Code, 2009 Edilion, unless stated othenvise. <br />In order for :he processing of your application to continue, it wiil be necessary to <br />provide the Ruilding Division with two complete new sets of construction <br />documents reftecting the corrections requested. <br />1. IBC 1023.5 limit, openings inCo exit passageways to those necessary for exit access to <br />the exit passagew�ay from norrr�ally occupied spaces and for egress from the exit <br />passageway. IBC 402.4.6 allows openings from mall exit passageways into mechanical <br />rooms, electrical rooms, building service areas and service elevators. The proposed <br />plans indicate storage rooms C& D with openings into ihe exit passageway which is <br />prohibited. <br />Z. IBC 715 requires a minimum fire door assembly rating of 1 hour for all exit enclosure <br />openings. This should be indicated in the plans. <br />3. The plans should include the adequate information to provide compliance �vith IBC <br />1023.6. All penetrations, proposed and existing, must comply with IBC 713. This <br />indudes membrane penetrations. <br />q. The plans should include adequate information to provide compliance with all of the <br />illumination requirements for IBC 1006 in the exit passageway. <br />5. The plans should include adequate information to provide compliance with all of the exit <br />sign requirements of IBC 1011 in the exit passageway. <br />If you have any questions, please call me at 425-257-7264. <br />CITY O� EVERETT � 3200 Ceaar Sireel • Everett, 1��iA 96201 •(425) 257-8800 � Fax (425) 257-8882 <br />ti JCom�non ClvicalS�tillcrW IO]Ui.01� tlmouyL �I6 pa0] Si' Gcnen �LII lCa>) doc <br />