Laserfiche WebLink
�,, , . <br /> , <br /> � j a�,:�-�,. <br /> ,, � �� <br /> .-, <br /> lIITIGIITION REQUIRED BY EXISTZNG CODES AND ORDZNANCES <br /> la. One (1) fire hydrant is required within 100 driving feet of the � <br /> ��� Fire Department connection to the sprinkler system will be <br /> ��� required. <br /> r H ti lb. Based on the proposed 9,700 square feet of Type V-N, sprinklered <br /> H � construction, fire flow of 1,50U GPM is required. <br /> y H <br /> � H� lc. Portable Fire Protection is required. A portable fire extinguisher <br /> � H� with a minimum UL Ra:.ing of 2A must be provided within 75 feet <br /> �'�' travel diatance of all portions of each building during <br /> � x� construction and prior to occupancy. Portable Fire protection <br /> �d must be provided throughout the building as required b� Article lU <br /> H <br /> of the Uniform Fire Code prior to the issuance of any Certificate <br /> H [�a g of Occupancy. <br /> (�]Y (� <br /> x7 y� id. Sprinkler system complying with Uniform Building Code Standard <br /> t� 38-1 and/or NFPA Standard 13 is required. Plans for any such <br /> g �N system must be submitted to the Building Department and/or Everett <br /> � d y Fire Department for review and approval. Suctt plans must include <br /> the proposed plan for the underground mains that will supply the <br /> ��j sprinkler system. Underground sprinkler piping must be <br /> � o y hydrostatically tested as established in accordance with NFPA <br /> Standard 13. Underground piping must be hydrostatically tested and <br /> flushed as established in accordance with NFPA Standard 24 for <br /> private Fire mains. All such tests must be witnessed by an Everett <br /> Fire Department's Znspector. Call 259-8731 to make appointment for <br /> such inspection. <br /> � .� All fire sprinkler contractors must be in compliance with the <br /> � ,,,� State of Washington�s new "Fire Sprinkler Contractors Licensinq <br /> Act." Please contact Deputy State Fire Marshal Mike Paddock at <br /> (206) 753-2200 for more information. <br /> �'"'� le. When access to or within a structure or an area is unduly <br /> difficult because of secured openings, or where immediate access <br /> --�. is necessary for life saving or fire fighting purposes, the Fire <br /> �� Department may recommend or require a key box to be installed in <br /> an accessible location. A rapid entry system may also be desirable <br /> in order to avoid unnecessary damage while making entry to any <br /> �� "'� building during an emergency situation. Please call (206) 259-8726 � <br /> �'� for further information. ! <br /> ' if. In accordance with Article 10.208(a) of the Uniform Fire Code, <br /> �.. ,�, approved numbers or addresses shall be placed on all new and <br /> existing premises, buildings and apartments, in such a position as <br /> to be plainly visible and legible from the street/road fronting <br /> ( � � trie property and access roads within the apartment complex. The <br /> size, material, exact location, and contrasting background must be <br /> reviewed and appreved by the Public Works or Fire Department. <br /> � , (SEPA Public Servici�s and Utilities Policies) <br /> r <br /> 3 <br />