� <br />SM,ITH AUTO SHOP <br />NB JOB 91133C <br />PAGE 2 <br />II. VOLUME OF STORAGE RE UIRED <br />Vt = VS X A X Cfut = 1667 CF <br />PLAN BY KEGEL HAS STORAGE VOLUMES AS rOLLOWS: <br />�• CB �1 353 CF <br />�� #2 666 CF <br />CB #�3 353 CF <br />SUBTOTAL 1372 CF <br />STORAGE IN PIPE <br />8" PIPE, AREA = 0.35 SF <br />TOTAL L.F. OF PIPE IS 322 FEET <br />VOLUME STORED IS 112.7 CF <br />CB'S AND FLOW CONTROL <br />STRUCTURE 35 CF <br />TOTAL VOLUME 1519.7 = 1667 <br />THIS CHECKS WITH VOLUME CALCULATED. <br />SINCE THE PAVEMGNT AND EXISTING CB $�1 AND #3 ARE NOT <br />BRING ALTERED, WE WILL DETERMINE ONLY THE 25 YEAR <br />STORAGE AREA FOR THE NEW AUTO SHOP. <br />III. PLANINETER THE SURFACE AREA FOR THE BASIN TO STORE A <br />THIRD OF THE 1667 CF OP STORAGE REQUIRED (MINUS PIPE <br />CAPACITY AND rg�S). <br />1667/3 - S55 CF <br />