Laserfiche WebLink
.. .. __ l -t1. � . <br /> July 26, 7971 <br /> ;1;�_ . . <br /> CITY OF <br /> evere1l.� <br /> QTY NALL � 359���U5 <br /> EVERETT. W�5111NGTON <br /> 9U301 <br /> INSPECTION OEP�HTMLNT <br /> Kimpton Electric <br /> 18916 - 96th Avenue N.W. <br /> Stanwood, Washingtrn 98292 <br /> Re: 4706 Forest Drive, Everett, Washington <br /> Dear idr. Kicipton: <br /> An electrical final was made at ehe above address and ;:he following will <br /> have to be corrected. All outlets, old and new within seven feet of a <br /> grounded object must be grounded. There are outlets that will fall under <br /> this requirement. Also there are several grounded outlets installed <br /> that are not grounded, The N.E.C. in section 210-7 states that Receptacles <br /> � and cord cannectors equiped with grounding contacts shall have those <br /> contacts effectively grounded, <br /> Would you please call for a re-inspection when these corrections are <br /> madeY <br /> Yours truly <br /> L. J. Dougherty <br /> Electrical I:�spector . <br /> L7D:eb <br /> 7 <br />