Laserfiche WebLink
Construction <br /> ]. Units A, B & C. I can not locate the attic ventilation calc's (A, B & C) or locations of <br /> vents (B & C) other than bird blocking. <br /> 2. Unit C. The size of the strip footing on Sheet 13 should be sho�v��. <br /> 3. Units A, B & C. The spread footings should be shown as minimum 24"square on <br /> each building per tlie Geo-tech report. <br /> 4. Unit C. A detail for the watcr proof deck shoufd be provided. <br /> � Accessibility <br /> 1. Uuit HC. The grab bar for bach of the transfcr shower(or blocking) should be noted <br /> on the plans. Section 1106.27.2.1 <br /> Please prepare a response letter sho�ving where each item in this :ettcr is addressed on the <br /> plan set. <br /> Upon submittal of thc drawings, you application will be given priority and plan review <br /> will recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to <br /> ensure that the proposed structurc will bc constructed in compliance with all adopted <br /> codes. <br /> Sincerely, <br /> � <br /> i' <br /> Tony Lee <br /> Associate Engineer <br /> TL:jcb56876 <br /> �'-� / <br /> �ia <br /> �� <br />