Laserfiche WebLink
23. Portablc Pirc Pruiection - A portablc tire extinguisher ���ith a minimunt U.L. rating of 2-A:10-f3:C <br />shall bc providcd within 7S fcct of travcl on all �loors of cach Uuilding during construction and <br />prior to occupancy. <br />2d. Pire Alann System - An approved automatic fire detection system shall be provided as mquired hy <br />City Ordinance No. 1902-92, Chap[cr 16.76, of thc Gverett Municipal CoJe. <br />Plans for such system shall be submittcd to the Pire ��larshal for nview and approval prio� to <br />installation. Submival shall incluJe cut shects of all cyuipment intcnded f'or use. Appropriate trip <br />tests, wiuiessed by a Fire Deparunent inspeclor, shall he performed, along with a certificate of <br />complction, n���,�� «� r�,�i acccptancc of thc sysiem. <br />I�irc alarm syslems shall bc inslalled accorJing ro NPPA Standard 72. Installation of firc alarm <br />components, incluJing basic wiring, may not conunencc before plans are approved by thc Pire <br />Dcparunent Plan Rcvicwcr. Pire alann Jrawings must bc professionally rendered, in sufficicnt <br />dc�ail, and must bc intcrnally consistcnt. Riscr diagrtuns must match installation plans and load <br />calculations. Cumponcuts must bc listcd and approved for use together. Changes to plans must <br />include ncw drawings and calculations and must be approved by the Fire Department Plan <br />Reviewer prior to installation. Pire alann installation is suUject to ticld inspection by a Firc <br />I)eparttncnt Inspc�tor. :\n approvcd sct of plans and the I3uilding Deparlment clectrical pennit <br />rnusl be present fur ,my installation inspection. <br />Pire alarm syslems shall be installed under permit of �he City of Gvcreu BuilJing Deparhnent. <br />I:Icctrical inspections and approval are rcquired prior lo c.illing for acceptauce tests. Please call <br />(425) 257-8810 liir pcnnit information. <br />2�. I�irc Suppressiun (SPrinklcr) S1'stcm -:\n a��pro�cd awumutic suppression s)'stcro shall hc pro��idcd <br />as rcyuircd by City Ordinanc� No. l9C`<'-92, Chaptcr 16.76, uf thc L'vcrett Municipal CoJc. 'I'hc <br />system must include a mechanical �vatcr gc;ng helL Plans for any such system shall he subtnitted to <br />ihe I3uilding lleparlmcut lor esaminatio❑ and appruval. Such plans shall indude i�lans Ibr the <br />underground mains that ���ill supply the sprinkler system. <br />?G. "I'hc type of sprinklcr lu bc installcd will he determined by the I3uildi�ig Oflicial. It may be an <br />NI�Pr\ 13, NPPA 13R, or NPPr\ 13ll system depenJing upon scveral fa�tors. Sprinklcr <br />installation shall not begin ���ithout an approved and stmnped set of plans from thc Quilding <br />Ucpariment. 'I'I�c 1'irc Department �vill also rcvicw the plans and shall tield inspcct tl�e installation <br />baseJ only on approved plans that must hc on sita Changes to plans must be approved by both thc <br />13uilding anJ Pirc Dcpculmcnts. <br />Ahuveground sprinkler piping shall be IiydrostaticallV tested as established in NPPA Standard 13. <br />llndcrground piping shall hc hydroslatically tcstcd and Ilushcd as �stablishcd in Ni'PA Standard 2a <br />for privatc fin mains. Bclo���-ground piping nmsl bc inst:illed by �i:isl�iugton Statc Yatrol <br />I.iccused Undcrground Sprinklcr linc ccrliticd "U" iustallcrs. For furthcr information, <br />coutact the State Fire �larshal's OfGce at (3G0) �^L'-313d or wntact the Everett Fire <br />Dcparlmcnt at (425) 257-8123. All such tcsts shall hc witnes;cd by a Pirc Dcpartmcnt inspccror. <br />Call (d25) 257-5123 tu makc an ,ippoinunent for inspcclion. <br />% <br />7 <br />