Laserfiche WebLink
6. A detail should be provided which shows the weather-barrier condition betwecn the <br /> walls and floor slab. <br /> -�"7. The plan notes should specify the chosen energy code compliance option for the <br /> building envelope, mechanical, and lighting components. The enclosed forms should <br /> be completed and returned with the plan revisions. Note that qualification of a semi- <br /> heated space requires the specifications listed in Section 1310.2 to be followed, as well <br /> as verification, per an energy budget, to be submitted. <br /> 8. The plans are generally too insuf5cient to provide a complete swctural review. <br /> Calculations and details should be provided by a licensed Washington State engineer <br /> for the total vertical and lateral load resistance systems of the structure. <br /> Prepare a responsc letter showing where each item in this correction let[er is addressed on <br /> the plan set. <br /> Upon resubmital oF the drawings, your application will be given priority and plan review <br /> will commence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to <br /> cnsure that the proposed swcture will be constructed in compliance with all adopted <br /> codes. <br /> Sinccrely. <br /> �i��� <br /> Tony Lce <br /> Associate Engineer/I3uilding <br /> T�:�n:Hs�ssa <br />