Laserfiche WebLink
� <br /> ('� � .�.. <br /> Ea�:�r <br /> � ,�-- <br /> ,:� <br /> ! : ':��.. <br /> ' November 3, 1980 <br /> CITY OF <br /> everett <br /> gimmons Design Builders, Inc. <br /> Globa I3uilding cin N��� • ae�.ea�e <br /> ry¢��}}.WAlNIHOTON <br /> 9725 S.E. 36th� SU1tC 214 •eao� <br /> Mercer Island, washington 98040 IN�P[CTIOM O[PhNTNCNT <br /> Attn: Mr. Robert Shubert <br /> SDBJECT: 1918 �erett Avenuc. <br /> LTD Partnership Building <br /> The twentp-cninute fire-rated corridor doors and frames for the above <br /> project are in compliance with the 1979 Uniform Building Code; however, <br /> the hinges and latches do not meet Code requirements. <br /> Section 3304(h) of the Uniform �uilding Codc requires that tlie smoke <br /> and draft control door assemblies have a fire-protecticn rating of not <br /> less than twenty minutes when tested in accordance with U.B.C. Staradard <br /> No. 43-2 without the hose strcam test. <br /> The U.D.C. Standard No. 43-206(c) requires the door hardware to Ue <br /> evaluated in the testing procedure and a report of the hardware in thc <br /> test report (Sec. 43-2081 • <br /> The Installation Standards as set forth in the Cal-Wood '.00r Test <br /> Report No. WH1 specifies that the installation be in compliance with <br /> N.F.P.A. - 80. <br /> N.F.P.A. Sec. 3-8-1 requires only labeled firc door hasdware to be used. <br /> (See N.B.F.U. definition of "labeled".) <br /> I trust that tliis information clarifies Code requirements relative to <br /> the corridor doors. <br /> '� Sinccrely, <br /> ' .._.,._ �1. _. �. . <br /> Kenneth W. Callahan, � <br /> Buildin9 Director <br /> enc. <br /> cc: tlo�•:ard ,tattesott <br /> poug F3udden <br /> l4ally Christopher�on <br />