�ti��, P�lBL/L f�!/OR/�C5 �:�=.�,� „�,; �:-�;,��;_: <br />c.�;�;� �v ! �/4 � 13 � <br />I.__. _.. .__.__�_I <br />March 1, 2013 <br />Ms. Jessica Rooinson <br />Crown Fire Protection, Inc <br />P.O. Box 12113 <br />Mill Creek, WA 98082 <br />Project: Modification to sprinkler layout for Burlington Coat Factory <br />Job Address: 1402 SE Everett Mall Way <br />Plan Review No: K1302-007 <br />Dear Ms. Robinson, <br />In response to the recent application for a new suppression construction permit, the plans have <br />been examined and you are advised that the permit review cannot be resumed until the <br />following issues are resolved. <br />1. A double-check detector valve assembly (DCDA) should be shown on the drawings to <br />replace the single check detectors serving this space. The buildir,g owner should have <br />received correspondence from Tim Markham, Everett Cross-Connection Specialist, earlier <br />this year. According to our rerords, fhis tenant space is currently being served by a <br />single-check detector. <br />2. All replacements of a sin9le check detector to a double r_heck detech�r will need to be <br />installed by a private contractor, since the ciry only installs new services upon request. <br />3. The fire service for the tenant space should be shown from the tenant: space to the city <br />main, induding the cross connection. <br />4. Standpipe revisions are required to be shown on the drewings, per IBC 905.3.3. <br />5. The revised sprinkler submittal will require three copies of the following, so that the <br />submittal can be revi�wed: <br />a. A catalog cut indicating the DCDA manufacturer's modei in the 'Backflow <br />Prevention Assemblies Approved for Installation in Washington State', published <br />by the Washington State Department of Health, current edition. <br />b. A plan and section of the intended location and installation of the DCDA. The <br />DCDA can he located in an interior or an exterior location, to comply with City of <br />Everett Standard Construction Drawings 515 or 523, attached. <br />c. The model number of the DCDA should be sho�vn on the drawings. <br />d. ��he routing of the fire service from the city main should be shown relative to the <br />property line of the building. <br />e. The riser room should be identified on the pians. <br />All plan sheets affected by these revisions should be resubmitted (three copies each). Prior to <br />submitting revisions, I recommend that you resolve any outstanding questions that you may <br />have about tliis corrections letter, to speed up tl�e process of permit issuance: <br />