2001
<br />State Nonresidential Energy Code Com ce Form
<br />Prescriptive Spaces 10ccupancy: Q Warehouses, storage areas or aircraft storage hangers *Other
<br />Note: If occupancy type is -Other and future
<br />answer is Checked, the number of tenures in
<br />the space is not limited by Code. Clearly
<br />Indicate these spaces on plans. Ifnot
<br />qualified, do LPA Calculations.
<br />Fixtures: ❑ Check here if at least 95% of fixtures in the space meet all four criteria:
<br />1. Fixtures are fluorescent, non -tensed, with only one or two lamps, and
<br />2. Lamps are T-1, T-2, T-4, T-5, T-6, T-8 3. Lamps are 5.50 Watts, and
<br />4. Ballasts are electronic ballasts 5. Exit lights < 5 watts/fixture
<br />6. Screw4n compact fluorescent fixtures do not qualify
<br />TABLE 15-1 Unit Liahtina Power Allowance (LPA)
<br />Use
<br />LPA
<br />Is
<br />Use
<br />LPA
<br />15
<br />Painting, welding, carpentry, machine shops
<br />2.3
<br />Police and fire stations
<br />1.5
<br />Barber shops, beau shops
<br />2.0
<br />Atria atriums
<br />1.0
<br />Hotel ban uet/conferencelexhibilion hall"4
<br />2.0
<br />Assembly spaces , auditoriums, gymnasia', heaters
<br />1.0
<br />Laboratories
<br />2.0
<br />Group R-1 common areas
<br />1.0
<br />Aircraft repair hangars
<br />1.5
<br />Process lams
<br />1.0
<br />Cafeterias fast food establishments
<br />1.5
<br />Restaurenmlr,
<br />1.0
<br />Factories, workshops, handirm areas
<br />1.5
<br />Locker and/or shower facilities
<br />0.8
<br />Gas stations, auto repair shops'
<br />1.5
<br />Warehouses", storage areas
<br />0.5
<br />Institutions
<br />1.5
<br />Aircraft storage hangars
<br />0.4
<br />Libraries
<br />1.5
<br />Retail . retail banking
<br />1.5
<br />Nursing homes and hotellmotel guest rooms
<br />1.5
<br />Parking garages
<br />See Section
<br />1532
<br />Wholesale stores(pallet rack shelving)
<br />1.5
<br />Mall concourses
<br />1.4
<br />Plans Submitted for Common Areas Only'
<br />Schools buildings (Group E occupancy only),
<br />school classrooms day care centers
<br />1.35
<br />Main floor building lobbies (except mall
<br />concourses
<br />1.2
<br />Laundries
<br />1.3
<br />Common areas, corridors, toilet facilities and
<br />washrooms, elevator lobbies
<br />0.8
<br />Office buildings, offtce/administrative areas in
<br />facilities of other use types (including but not limited
<br />to scheatss hospitals, institutions, museums, banks,
<br />churches
<br />__T
<br />1.2
<br />Footnotes for Table 15.1
<br />11 In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use is not
<br />mentioned specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based
<br />upon the most comparable use specified in the table. See Section 1512 for exempt areas.
<br />2) The watts per square foot may be increased, by two percent per fool of ceiling height above twenty feet, unless specifically
<br />directed otherwise by subsequent footnotes.
<br />3) Wafts per square foot of room may be increased by two percent per fool of ceiling height above twelve feet.
<br />4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
<br />5) Watts per square foot of room may be increased by two percent per fool of ceiling height above nine feet.
<br />6) Includes pump area under canopy.
<br />7) In cases in which a lighting plan is submitted for only a portion of a Door, a Unit Lighting Power Allowance of 1.35 may be used
<br />for usable office floor area and 0.80 walls per square foot shall be used for the common areas, which may include elevator
<br />space, lobby area and rest rooms. Common areas, as herein defined do not include mall concourses.
<br />8) For the fire engine room, the Unit Lighting Power Allowance Is 1.0 walls per square root.
<br />9) For Indoor sport tournament courts with adjacent spectator seating, the Unit Lighting Power Allowance for the court area is 2.6
<br />walls per square foot.
<br />10) Display window illumination Installed within 2 feet of the window, lighting for free-standing display where the lighting moves with
<br />the display, and building showcase illumination where the lighting is enclosed within the showcase are exempt.
<br />An additional 1.5 wl8' of merchandise display luminaires are exempt provided that they comply with all three of the following:
<br />a) Iowted on ceiling -mounted track or directly on or recessed Into the ceiling Itself (not on the wall).
<br />b) adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with
<br />two points of track attachment).
<br />c) fitted with tungsten halogen, fluorescent, or high intensity discharge lamps.
<br />This additional lighting power is allowed only if the lighting is actually installed.
<br />11) Provided that a floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be
<br />defined, for computing the interior Unit Lighting Power Allmvance, as the floor area not covered by racks plus the vertical face
<br />area (access side only) of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by
<br />racks.