2006 Was' qton Slate Nonresidential Energy Code Compli" ce Form
<br />Nonmr : 1i
<br />anc J Warehouses, storage areas or aircraft storage hangers _)Other
<br />Prescriptive Spaces Occupancy: p r•
<br />Qualification Checklist
<br />I Lighting
<br />Check if 95%or more of fixtures comply with 1,2 or 3 and rest are ballasted.
<br />Note: If occupancy type is "Other" and
<br />Fixtures:
<br />(Section
<br />1. Fluorescent fixtures which are non -lensed with a) 1 or 2 two lamps, b) reflector
<br />fixture onswer is checked, the ncmber of
<br />Code.
<br />1521)
<br />or louvers, c) 5-60 watt T-1, T-2, T-4, T-5, T-8 lamps, and d) hard -wired elec-
<br />fixtures in the space is not limited by
<br />Clearty indicate these spaces on plans. If
<br />tronic dimming ballasts. Screw -in compact fluorescent fixtures do not qualify.
<br />not qualified do LPA Calculations.
<br />2. Metal Halide with a) reflector b) ceramic MH lamps <= 150w c) electronic ballasts
<br />3. LED I
<br />I AM= -10-1 Un It "IU It urty rawer
<br />LPA W/s
<br />Use
<br />LPA W/s
<br />Use
<br />Automotive facility
<br />0.9
<br />Office buildings, office/administrative areas in
<br />1.0
<br />facilities of other use types (including but not limited
<br />to schools. hospitals, institutions, museums, banks,
<br />churches1,
<br />Convention center
<br />1.2
<br />Penitentiary and other Group 1-3 Occupancies
<br />1.0
<br />Courthouse
<br />1.2
<br />Police and fire stations
<br />1.0
<br />Cafeterias, fast food establishmentsir- ,
<br />1.3
<br />Post office
<br />1.1
<br />restaurantslbars'
<br />1.0
<br />Retail retail banking, mall concourses, wholesale
<br />1.5
<br />Dormitory
<br />.
<br />stores allet rack shelving)
<br />1.0
<br />School buildings (Group E Occupancy only), school
<br />1.2
<br />Exercise center
<br />classrooms, day care centers
<br />Gymnasia'. assembly spaces'
<br />1.0
<br />Theater, motion picture
<br />1.2
<br />1.6
<br />Health care clinic
<br />1.0
<br />Theater, rforming arts
<br />1.0
<br />Hospital, nursing homes, and other Group 1.1 and
<br />1.2
<br />Transportation
<br />1.2 Occupancies
<br />Hotel/motel
<br />1.0
<br />Warehouses". storage areas
<br />0.5
<br />Hotel ban uellconference/exhionion hall
<br />2.0
<br />Workshops
<br />1.4
<br />1.8
<br />Parking garages
<br />0.2
<br />Laboratory spaces (all spaces not classified
<br />-laboratory' shall meet office and other appropriate
<br />categories)
<br />Laundries
<br />1.2
<br />1.3
<br />Plans Submitted for Common Areas Only'
<br />Libraries
<br />Manufacturing facility
<br />1,3
<br />Main floor buildin lobbies (except mall concourses
<br />1.2
<br />Common areas, corridors, toilet facilities and
<br />0.6
<br />1.1
<br />Museum
<br />washrooms, elevator lobbies
<br />Footnotes for Table 15-1
<br />1) In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use is not mentioned
<br />specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most
<br />comparable use specified in the table. See Section 1512 for exempt areas.
<br />2) The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically directed
<br />otherwise by subsequent footnotes.
<br />3) Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet.
<br />4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
<br />5) Watts per square foot of room may be increased by two percent per foot of ceiling height above nine feet.
<br />6) Reserved.
<br />7) For conference rooms and offices less than 150ft' with full height partitions, a Unit Lighting Power Allowance of 1.10 w/ft' may be used.
<br />8) Reserved.
<br />9) For indoor sport tournament courts with adjacent spectator seating over 5,000, the Unit Lighting Power Allowance for the court area is
<br />2.60 Wlfl'.
<br />10) Display window illumination installed within 2 feet of the window, provided that the display window is separated from the retail space by
<br />walls or at least three -quarter -height partitions (transparent or opaque). and lighting for free-standing display where the lighting moves
<br />with the display are exempt.
<br />An additional 1.5 wlfl' of merchandise display luminaires are exempt provided that they comply with all three of the following:
<br />a) located on ceiling -mounted track or directly on or recessed into the ceiling itself (not on the wall).
<br />b) adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two points
<br />of track attachment).
<br />c) fitted with LED, tungsten halogen, fluorescent, or high intensity discharge lamps.
<br />This additional lighting power is allowed only if the lighting is actually installed.
<br />11) Provided that a floor plan, indicating rack location and height. is submitted, the square footage for a warehouse maybe defined, for
<br />computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only)
<br />of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by racks.