Laserfiche WebLink
Mr. Jack Chesbro <br />May 15, 1973 <br />Page 2 <br />8. <br />Recessed light fixtures must have L'L enclosure, as <br />required by <br />Rating Bureau. <br />9. <br />Panel A is 480/272 in lieu of 120/208 and <br />Panel B <br />is 120/208, <br />(plan note). See riser diagram. <br />10. <br />100 amp switch and fuse in Meter Room #1 . <br />Service <br />conductor to <br />tenant space is 4 k3 TH11 (cu.), 1 1/4c. <br />11. <br />Service to roof top unit (480 V, 3 phase) <br />should be <br />from Panel A. <br />Electric heat, as specified, will overheat <br />30 KVA <br />transformer. <br />Recheck wire sizes. <br />12. <br />Return air must be ducted to unit. <br />13. <br />Need toilet exhausts. <br />14. Roof top unit delivers 6,000 CFM, check number of supply and return <br />grilles. <br />15. Roof top unit to be mounted on integral roof curb. <br />Very truly yours, <br />ROY E. CALVIN, AIA ARC T <br />Cam- _ <br />Carrol E. Littlejohn <br />Architect <br />CEL/dh <br />cc: Mr. Bill Behn <br />Mr. Bob Moore <br />Mr. Dudley Morris <br />bcc: Mr. John Farrens <br />f2nnn�� <br />MAY 17 1973 <br />CITY OF EVERETT <br />Inspection Dept. <br />