Laserfiche WebLink
Ltr. (B0409-026) <br />October 1, 2004 <br />Page 2 <br />� <br />6. Exit signs should be internally or externally illuminated. Back•up power capable of 90 <br />minutes of operation should be provided. Sections 1011.2 & 1011.5.3 <br />7. Tactile exit signs should be provided. Section 10113 <br />8. Maximum occupant load signs should be shown on the plans for both assembly rooms <br />(the proposed number should be specified). Section 1004.3 <br />9. Exit illumination emergency powar should be provided at the following locations: <br />illumination of the access Isles leading to the required exit doors within each assembly <br />room and the portion of the exterior exit discharge immediately adjacent to exit discharge <br />doorways. Section 1006.3 <br />10. A minimum of five water closets should be provided for women (based on a gaming iloor <br />azea of 3505 square feet+ 25 persons in the restauranUbar area). Section 2902. L 1 <br />] L The hallway(s} accessing the toilet rooms should be a minimum oC 42" wide (4R" if. the <br />doors have closers provided) to provide required maneuvering clear�nces. Section . <br />404.2.4 ICC/ANSI A 117.1-1998 <br />Please prepare a response letter sho�ving where each item in this correction letter is addressed .�n <br />the plan set. <br />Upon resubmission of the drawings, your application will be given priori[y and plan review will <br />recommence. <br />All required submittals must be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />'l .%�-'- <br />Tong�R. Lee <br />Plans Examiner <br />a�a <br />