'UBL/C f�0'R/CS <br />November 21, 2012 <br />Rose & ]ose de.lesus <br />607 SE Everett Mall Way, Suite KL <br />Everelt WA 98208 <br />RE: Owner. Robinson Properties, Inc, LLC <br />Job Address: 607 SE Everett Mall Way <br />Plan Check No: M1206-031 <br />Dear Ms/Sir: <br />In the pursuit of a code compliant Type-i hood installation, it is imperative that you provide an <br />accurete set of construction documents. The documents, as submitted, have yet to address the <br />following issues: <br />1. IMC 507.12 requires the hood to overhand the cooking equipment by 6" on all open <br />c?�es. See Figures 507.12(1) &(2), enclosed. <br />2. After the overhangs are provi�led by Item 1 above, what wiil be the clearance� between <br />the hood and the combustible walls on the sides? Please provide dimensioned and to- <br />scale cross-section details showing the relationships between the hood and the walls. <br />Since the walls are combustible, you would need to have 18" of clearance or provide <br />one of the clearance reduction methods of IMC 308, Table 308.6 (enclosed). IF using <br />clearance reduction, show all materials and spacings. <br />3. The submitted drawings indicate 10" of clearance between the to;: of the hood and the <br />combustible ceiling/roof assembly. If it is the intent to use a cl�arance reduction <br />method from IMC 308, please provide a dimensioned and to-scale cross section showing <br />all materials and spacings. <br />Please provide 2 copies of the revised drawings. <br />Sincerely, <br />� �� ��� <br />Steve Miller <br />Associate Engineer <br />CITI' OF EVERETT • 3200 Cedar Street • Everelt, WA 98201 •(425) 257-6800 • Fax (425) 257-8882 <br />s�in,��m��•a<���acs�eu<„>n:o�.,�n �rov s[ r.�mi m,n w,ri a�K <br />