�� <br />� <br />August 10, 2012 <br />Ms. Jessica Robinson <br />Crown Fire Protection, Inc <br />P.O. Box 12113 <br />Mill Creek, WA 98082 <br />PVBL/C N/�/Zi IC5 <br />Project: Modification to sprinkler layout for pollar Tree <br />]ob Address: 811 SE Everett Mali Way <br />Plan Review No: K1207-010 <br />Dear Ms. Robinson, <br />In response to the recent application for a new suppression construction permit, the plans have been <br />examined and you are advised that the permit review cannot be resumed until the following issues are <br />resolved. <br />1. A double-check detector valve assembly (DCDA) should be shown on the drawings to replace the single <br />check detectors serving this space. The building owner should have received correspondence from Tim <br />Markham, Everett Cross-Connection Specialist, earlier this year. According to our records, this tenant <br />space is currently being served by a singlP-check detedor. <br />2. All replacements of a single check detector to a double check detector will need to be installed by a <br />private contractor, since the city only installs new services upon request. <br />3. The fire service for the tenant space should be shown from the tenant space to the city main, including <br />the cross connedian. <br />4. The revised sprinkler submittai will require three copies of the following, so that the submittal can be <br />reviewed: <br />a. A catalog cut indicating the DCDA manufacturer's model in the'Backflow Prevention Assemblies <br />Approved for Installation in Washington State', published by the Washington State Department <br />of Heaith, current edition. <br />b. A plan and sedion of the intended location and installation of the DCDA. The DCDA can be <br />located in an interior or an e�erior location, to comply with City of Everett Standard <br />Construction Drawings 515 or 523, attached. <br />c. The modei number of the DCDA should be shown on the drawings. <br />d. The routing of the fire service from the city main should be shown relative to the proper[y line <br />of the building. <br />e. The riser room should be identified on the plans. <br />f. A post indicator valve (PIV) is required if there is not direct access to the riser room from <br />outside of the building. <br />g. All plan sheets affected by these revisions. <br />h. All hydraulic calculations affected by these revisions. <br />If you have questions about the backtlow requirements identified on the attached owner notification, please <br />contact Tim Markham at 425-257-8833. If you have questions about the PIV or other fire service equipment, <br />piease contact Assistant Fire Marshal ]iin Venturo at 425-257-8124. I can answer any questions that may <br />come from this corrections letter. <br />