Laserfiche WebLink
� �: <br /> icUruary 26, 1973 <br /> �r��� ��. � ;.- � � <br /> CITY OF <br /> everett <br /> QTY NAI� � :59�Oo05 <br /> William Arid Johnson & Associates, Architects E��Acr.. w.s�����,o�, <br /> aa:o� <br /> 35�6 pjj.'O$dW'a�Y � INSPECTION OEPARTMENT <br /> Evcrett, Wastiington 98201 <br /> Reference: IIethany Mansion of Hope <br /> 3315 LomUard <br /> Everett, 4lashington <br /> 7�+pe 5, 1-hour, Group II, Fire Zone 2 <br /> Gentlemen: <br /> The follocaing items must be corrected to comply with the Uniform Building <br /> Code, 1970 Edition: <br /> 1. Two '�" layers of G.W.B. are not 2-hour fire resistive construction. <br /> 2-hour fire resistive construction requires two layers of 5/8" <br /> x-rated G.W.B. <br /> 2. Required 2-hour firc resistive construction must be carried thru <br /> floor and al-tic construction terminating at floor or roof sheathin;. <br /> Provide details showing method of ac};ieving the required protection. <br /> 3. The concrete slab between the parkinf and the main floor shall have <br /> a 3-hour fire resistive rating. <br /> 4. Door �lll to garUage, door �k10 to hal? and door �IS to hall in the <br /> basement musl' be 3-hour fire assemblies. <br /> 5. Wall separating stair core in basement shall be 3-hour fire resisCive <br /> construction. A 6" Urick wall is only 2-hour fire resistive consl-ruc- <br /> tion. <br /> 6. Atty duct work penetrating fire resistive walls or floors shall have <br /> fire dampers. <br /> 7. Shafts witl� floor openings shall Ue 1-hour fire resiseive construction, <br /> witli protecLive openings. <br /> II <br />