Laserfiche WebLink
January 23, 2009 <br />Karcy Swctl <br />5803 Lowcll Rd <br />Evcrett, WA 98201 <br />Re:5803 Lowcll Rd. <br />Dcar Mr. S���ctt <br />An inspcction was donc on Novembcr G, 2008 at 5803 Lowcll Rd. Thc following <br />dcficicncics wcrc notcd; <br />Plumbing Corrections: <br />1. Thcrc is only (1) 1 1/2" or 2" vent penetrating thc roof, probably from thc original <br />bathroom. Every fixturc has to bc vented properly <br />2. You must have the same cross-sectional area of venting as your waste sizc <br />3. Improper mcQiods throughout thc whole �vaste/vent system-- It is suggested to <br />replumb the �vholc baseinent area and provide the proper venting through the roof <br />4. Disl»vasher musl be connected through an approvcd air gap <br />Mechanical Corrections: <br />Watcr Hcatcr Corrcctions: <br />1. B-vent is back graded, must havc I/4" per lt gradc <br />2. Single wall B-vcnt nuist have a 6" clearance from combustibles <br />3. Musl have scismic straps or anchors to prevent movetncnt <br />4. Tcmperaturc and pressurc rclicf must bc pipcd to witl»n G' of floor <br />I�urnacc Corrcctions: <br />l. Rclum air Crom upstairs is not connccted to fivnacc <br />2. Openings in rectangular ducts should be covercd or utilized <br />3. .loints and scams of duchvork must bc taped or mastic <br />d. Hcat ducts for ncw Ucdroom covcred bcforc inspcction <br />F.Icctrical Corrections: <br />OB'PAIN LICENSBD ELGCTRICAL CONTKACTOR TO: <br />1. Meggcr all circuits in ne���, rcmodelcd, and rewired areas <br />2. Providc dctailcd as-built drawing <br />3. Repair or rewirc to bring affected amas in compliance with 2005 NFC <br />**Contractor to mccl ���ith Elcctrical lnspcctor prior to commcncing work <br />�O <br />