Laserfiche WebLink
Ltr. S. Beaver (C0706-003) <br />June 18, 2007 <br />Page 2 <br />8. The cut end of 8 rafters shall be full bearing on the ridge board. (A 2 x 6 rafter <br />requires a 2 x 8 ridge board.) <br />9. Provide smoke alarms in all sleeping rooms and in the corridor or area giving access <br />to each separate sleeping area. Smoke alarms shall comply with Section R313 IRC. <br />10. Verify clearances are met for bathroom tixtures per Table A307.2 IRC (copy <br />enclosed). <br />Please prepare a response letter showing where each item in this correction letter is addressed <br />on the plan set. <br />Upun resuUmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that Qie proposed struclure will be construc,ed in compliance with all adopted codes. <br />Sincerely, � � <br />Yi ��_ <br />Jeff Heilm n <br />Development Technician <br />OCDI/PI.YCAMSfR/IIHIL�fANICV106f10)159IS IAN'f:I.L R�) �-% " <br />