Laserfiche WebLink
r <br />I <br />SITG CHECK/SITE ASSESSMENT REPORT <br />September 1991 <br />Fire Station No. 5, Gasoline 'tank Site <br />Site History: <br />Date of Tank Iristellation: 1956. <br />Dates of Use: 1956 to May 15, 1991. <br />iI. Physical Tank System: 1- 1,000 qallon steel tanl: and piping <br />with galvanized 1 1/2" steel vent pipe and 2" steel, fill tube. <br />Product Stored: Gasoline, leaded and unleaded. <br />Type of Bedding: Pea gravel and glacial till. <br />Leak Detection System: <br />12/23/90. <br />Secondary Containment <br />Honitoring Wells: I�one <br />lJeekly tank gauging c+as done sirice <br />None <br />Narrat.ive: This U.S.T. spstem serves only the Cit�- of 6�•ereLt, <br />IFire Department vehicles. It was or:ned by Snohomish Count�• <br />, prior to annexation in about 1968 and has no hold do�•n slal,. <br />The dispenser was situated on the south�+est corner of the Fi�•e <br />I Station Buildin�. It has residenL•ial housing areas duwnste•eam <br />to the east and south, and is bordered on the north and west by <br />the major intersection commercial properLies. <br />III. History of Compliance and Performance: <br />Status of Regulatory Compliance: Prior to tightness tesL on <br />"!ay 15, 1991, the tank system was in compliance and constantiv <br />in use. - <br />Repair Records: \one available. <br />Current Permits: O.I:. <br />I' Previous Known i.eaks: No record in approximately fi�•e monclis of <br />gauging. <br />I Tightness Test: Positi��e leak on May 15, 1991. See attached <br />results. <br />Water Pump Outs: No record. <br />Ne:ghborhood Compla.ints: Vo record. <br />Fire nepartment Inspections: No record. <br />a.' <br />