Inspection of the Public Library <br />by Hills Collins & John Farrens <br />march 15, 1971 <br />Corrections necessary to make the building comply with the :xit requirements <br />of the Uniform Building Code. <br />1. The stair in the middle of the building which is part of the new <br />addition should not be considered an exit because of the location. <br />The location is such that it is not readily identified and it <br />would be difficult to direct the public to it's location. <br />a, remove exit light at top of stairs <br />b. remove exit light at bottom of stairs <br />2. The West exit from the auditorium should be accomplished by: <br />a. Installing a new exit light with directional arrow in ceiling <br />at the stair. The arrow should point away from the stair <br />toward the West. <br />b. Install an exit light over door in partition between the book <br />storage room and the reading room having the West exterior <br />exit. Light should be installed on storage room side. <br />c. Door swing in above mentioned partition to be changed to swing <br />in line of egriss; namely into the west reading room. <br />3. The North stair should he made into an exit enclosure by: <br />a. Adding a door and partition at the top level. Door should be <br />1-3/4" solid core with self closer with fusible link. The <br />door should swing into stairway. <br />b. An exit light should be installed over the above mentioned <br />door on the hall side. <br />c. At the main floor level the window openings into the stair <br />enclosure should be closed with a 1-hour construction. <br />d. A new 1-3/4" solid core door with self -closure with fusible <br />link should be installed at main level. Door shall swin- into <br />stair enclosure. Door may have a maximum of 100 square inches <br />of wire glass. <br />e. The door to the outside at grade level should have the padlock <br />removed and replaced with panic hardware. <br />f. At the basement level a new door and 1-hour partition should be <br />installed into stair enclosure. Door to be 1-3/4" solid core <br />with self -closer and fusible link. Install exit lite over <br />door. <br />g. Replace burned out exit light bulbs. <br />4. Add a new exit (door with exit light and metal fire escape) from the <br />South West corner of the addition. Fire escape to go to grade. <br />It is recommended that the open stair from the main floor to the basement in <br />the original building be closed. This can be done by removing stairs and building <br />a new floor in stair well, or enclosing the stair at bottom, or top with a 1-hour <br />partition with 1-hour door. This would make a fire separation between the base- <br />ment and the main floor. This open stair is the only violation of a fire separation <br />between the two floors and this weakness can be easily corrected. <br />