March 28, 2013 <br />• <br />0 <br />Dry 12Ce <br />�Vlf <br />VA LV E <br />EL r-1 <br />The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 <br />Telephone: 269-945.9501 Technical Services: 817-384-5464 Fax: 269.818-1680 Email: techsvcs@vikingcorp.com <br />bar/wrench, part number 02977BM <br />11 Close all auxiliary drains, the system test valve, and the priming water level test <br />valve on the dry valve trim The main drain (located on the inlet of the dry valve) <br />should remain open. <br />12, If equipped with a Viking accelerator and external anti -flood device <br />a. Close the X' (15 mm) anti -flood isolation valve. <br />b. Observe the air pressure gauge on top of the accelerator The gauge must <br />read zero before the accelerator will automatically reset It may be necessary <br />to loosen, remove, and re -install (use the appropriate wrench) the air gauge to <br />vent trapped air pressure from the upper chamber. <br />13. 01en the dry system air supply and establish desired system pressure See Table <br />3 for suggested au pressure to water pressure settings. NEVER EXCEED 60 PSI <br />(4.1 bar) AIR PRESSURE <br />Table 3 - Air Pressure Settings <br />Maximum <br />Water <br />Pressure <br />Minimum <br />Maximum <br />PSI <br />bar <br />PSI <br />bar <br />PSI <br />I bar <br />50 <br />3.45 <br />15 <br />1.03 <br />25 <br />1.72 <br />75 <br />5.17 <br />20 <br />1 <br />11.38 <br />30 <br />Y07 <br />100 <br />6.90 <br />25 <br />11.72 <br />35 <br />2.41 <br />125 <br />8.62 <br />30 <br />1207 <br />45 <br />3.10 <br />750 <br />10.34 <br />35 <br />2.41 <br />50 <br />3.45 <br />175 <br />12.07 <br />45 <br />3310 <br />60 <br />4.14 <br />14 Verify that the intermediate chamber of the dry valve is free of water. No water <br />should flow from the drip check when the plunger is pushed. <br />15. If equipped with a Viking accelerator and external anti -flood device: When pressure on the accelerator au pressure gauge <br />equals the system set pressure, OPEN and secure the V2* (15 mm) anti -flood Isolation valve <br />16. Slowly open the water supply main control valve. <br />17. When flow is developed from the main drain, CLOSE the main drain valve. <br />I & Fully open the water supply main control valve <br />19. Secure all valves in their normal operating position. <br />20 Notify Authorities Having Jurisdiction and those in the affected area that the system is in service <br />5. OPERATION (Refer to Figure 3) <br />The clapper (5) and air plate (11) assemblies combine to form a floating member assembly. With the clapper assembly (5) latched <br />closed, system air pressure forces the member assembly down, sealing the water seat (16) from the intermediate chamber. When <br />a sprinkler operates., the system air pressure is reduced. When system air pressure is reduced to the differential tripping point of the <br />valve, water supply pressure in the inlet chamber lifts the member assembly off the water seat (16) and flows into the intermediate <br />chamber. As the member assembly continues to rise, the hook assembly (15) is forced against socket set screw (23), which causes <br />the hook assembly (15) to pivot on hook rod (6b) and unlatch the clapper. The clapper is spring loaded and swings to a full -open <br />locked position (see Figure 2-A). <br />When using the optional accelerator, the accelerator senses the system air pressure drop and trips. Upon tripping, the accelerator <br />allows the system au pressure to enter the dry valve intermediate chamber, This immediately destroys the differential causing the <br />member assembly to rise faster <br />The intermediate chamber is normally at atmospheric pressure and is connected to the alarm line. When the valve trips, the interme- <br />diate chamber and alarm line are pressurized with system water pressure, activating alarms connected to the dry valve trim. <br />6. INSPECTIONS, TESTS AND MAINTENANCE <br />NOTICE: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM AND DEVICES IN PROPER <br />OPERATING CONDITION. <br />The Viking Model F-1 Dry Valve and trim must be kept free of foreign matter, freezing conditions, corrosive atmospheres, conlami <br />nated water supplies, and any condition that could impair its operation or damage the device. <br />It is imperative that the system be inspected and tested on a regular basis. The frequency of the inspections may vary due to con- <br />taminated water supplies, corrosive water supplies, corrosive atmospheres, as well as the condition of the air supply to the system. <br />For minimum maintenance and inspection requirements, refer to NFPA 25 In addition, the Authority Having Jurisdiction may have <br />additional maintenance, testing, and inspection requirements that must be followed. <br />WARNING: ANY SYSTEM MAINTENANCE WHICH INVOLVES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT <br />OF SERVICE IiiiFii E'.IMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY <br />ALL AUTHORITIES HAVING JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN <br />THE AFFECTED AREAS. <br />INSPECTION <br />Weekly inspection is recommended. If the system is equipped with a low air (or nitrogen) alarm, monthly inspections may be <br />adequate <br />1. Check pressure gauges located on the supply side and system side of the dry valve. Verify that the proper ratio of air (or <br />nitrogen) pressure to water supply pressure is being maintained (refer to Table 3). <br />