Laserfiche WebLink
• AMERICAN SPRINKLER CORP. • <br />2311 153RD AVE SE <br />SNOHbMISH,NA 98290 <br />HYDRAULIC CALCULATIONS FOR <br />DRAWING NUMBER: A1402 DATE: 5/17/14 <br />-DE IGN DATA - <br />OCCUPANCY CLASSIFICATION: ORDINARY HA2P.},D I <br />DENSITY: .15 gpm/sq. ft. <br />AREA OF APPLICATION: 1950 sq. ft. <br />COVERAGE PER SPRINKLER: 116 sq. ft. <br />TYPE OF SPRINKLERS CALCULATED' SSU <br />NUMBER OF SPRINKLERS CALCULATED: 18 <br />HOSE -STREAM DEMAND: 250 gpm <br />TOTAL WATER REQUIRED (INCLUDIt <br />FLOW AND PRESSURE (AT BASE OF <br />TYPE OF SYSTEM: DRY <br />WATER SUPPLY <br />G HOSE): 405.2 gpm <br />RISER):655.2 gpm @ 55.9 psi <br />Static: 75 psi Residual: 65 psi Flow: 1950 gpm <br />Source Elevation Relative to Finished Flow Level: 0 ft. <br />INSTALLING CONTRACTOR <br />Name: AMERICAN SPRINKLER C RP. <br />Address: 2311 153RD AVE SEISNOHOMISH,t•7A 98290 <br />Phone: 425-335-4645 Certification number:AMERISC087NC <br />NAME OF DESIGNER: SIEVE ADAMSON <br />AUTHORITY HAVING JURISDICTION! EVERETT FM <br />NOTES: <br />Calculations performed by HASS under license N 50110271 , <br />granted by HRS SYSTEMS, INC. <br />(Notes continue after pipe calculations results.) <br />A. gueluer <br />I•CEG te�etg i a <br />SpArklef CpfpofaGon I lnlo <br />4-�- 14 DS - von <br />