State Nonresidential Energy Code Com,t',nce Form
<br />Prescriptive Spaces
<br />Occupancy: O Warehouses, storage areas or aircr, fl storage hangers OQ Other
<br />Qualification Checklist
<br />Lighting Fixtures: ❑ Check here if at least 95%of fixtures in the space meet all four criteria:
<br />Note. If occupancy type Is rower and futtwe
<br />answer Is checked, the number of fixtures in
<br />1, Fixtures are fluorescent, non -lensed, with only one or two lamps, and
<br />the space is not limited by Code. Clearly
<br />Indicate these spaces on plans. If not
<br />2. Lamps are T-1, T-2. T-4, T-5, T-6, T-8 3. Lamps are 5-50 Watts, and
<br />qualified, do LPA Calculations.
<br />4. Ballasts are electronic ballasts 5. Exit lights < 5 watts/fixture
<br />6. Screw -in compact fluorescent fixtures do not qualify
<br />TABLE 15-1 Unit Liahtincl Power Allowance (LPA)
<br />Use
<br />LPA
<br />Is
<br />Use -
<br />LPA
<br />ISO
<br />welding, carpentry, machine shops
<br />2.3
<br />1 Police and fire stations
<br />1.5
<br />-Painting,
<br />Barbersho s. beauty shops
<br />2.0
<br />Atria atriums
<br />1.0
<br />Hotel banqueuconfnrence/exhibition halls''
<br />2.0
<br />Assembly spaces', auditoriums, gymnasia',
<br />1.0
<br />Laboratories
<br />2.0
<br />Group R-1 common areas
<br />1.0
<br />Aircraft repair hangars
<br />1.5
<br />Process lams
<br />1.0
<br />Cafeterias. fast food establishments
<br />1.5
<br />Restaumnts1b,
<br />to
<br />Factories, workshops. handling areas
<br />1.5
<br />Locker and/or shower facilities
<br />0.8
<br />Gao stations, auto re air shops
<br />1.5
<br />Warehouses", storage areas
<br />0.5
<br />Institutions
<br />1.5
<br />Aircraft story a hangars
<br />0.4
<br />Libraries
<br />1.5
<br />Retail , retail banking
<br />1.5
<br />Nursing homes and hotel/motel guest rooms
<br />1.5
<br />Parking garages
<br />See Section
<br />1532
<br />Wholesale stores(pallet rack shelving)
<br />1.5
<br />fvl:ill concourses
<br />1.4
<br />Plans Submitted for Common Areas Only
<br />Schools buildings (Group E occupancy only),
<br />school classrooms, day., care centers
<br />1.35
<br />Main floor building lobbies (except mall
<br />concourses
<br />1.2
<br />Laundries
<br />1.3
<br />Common areas, corridors, toilet facilities and
<br />washrooms. elevator lobbies
<br />0.8
<br />Office buildings, office/administrative areas 111
<br />facilities of other use types (including but not limited
<br />to schools' i hospitals. institutions, museums, banks,
<br />churches)
<br />7
<br />Footnotes for Table 15-1
<br />1) in cases in which a general use and a specific use are listed, the specific use shall apply. In cases In which a use is not
<br />mentioned specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based
<br />upon the most comparable use specified in the table. See Section 1512 for exempt areas.
<br />2) The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically
<br />directed otherwise by subsequent footnotes.
<br />3) Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet.
<br />4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
<br />5) Watts per square foot of room may be Increased by two percent per foot of ceiling height above nine feet.
<br />6) Includes pump area under canopy.
<br />7) In cases in which a lighting plan Is submitted for only a portion of a floor, a Unit Lighting Power Allowance of 1.35 may be used
<br />for usable office noor area and 0.80 watts per square fool shall be used for the common areas, which may Include elevator
<br />space, lobby area and rest rooms. Common areas, as herein defined do not Include mall concourses.
<br />8) For the fire engine room, the Unit Lighting Power Allowance is 1.0 watts per square foot.
<br />9) For Indoor sport tournament courts with adjacent spectator seating, the Unit Lighting Power Allowance for the court area is 2.6
<br />watts per square foot.
<br />10) Display window illumination installed within 2 feet of the window, lighting for free-standing display where the lighting moves with
<br />the display, and building showcase illumination where the lighting is enclosed within the showcase are exampt.
<br />An additional 1.5 wht' of merchandise display luminaires are exempt provided that they comply with all three of the following:
<br />a) located on ceiling -mounted track or directly on or recessed into the ceiling itself (not on the wall).
<br />b) adjustable In both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with
<br />two points of track attachment).
<br />c) fitted with tungsten halogen, fluorescent, or high Intensity discharge lamps.
<br />This additional lighting power is allowed only if the lighting is actually Installed.
<br />11) Provided that a floor plan, Indicating rack location and height, is submitted, the square footage for a warehouse may be
<br />defined, for computing the Interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face
<br />area (access side only) of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by
<br />racks.
<br />0�3