Laserfiche WebLink
MaV 28, 1976 <br />Pa�e 4 <br />2113. Dis�harge shall be piped to within ].8" of <br />the floor. Section 2108. <br />,/g, �rawings shall indicate how equipTotectedlfrom COoling <br />tower, pumps, piping, etc.) are p <br />freezing. Sections 2115 and Chapter 7. <br />,�, All equipment shall be sec or mourite�ion a level <br />base capable of supporting and distributing the <br />weight contained thereon. All boilers, tanks, and <br />equipment shall be securely anchored to the <br />structure. EqLioment requiring vibration isolation <br />shall be installed as designed bp a reqistered <br />engineer to the satisfaction of the Ruildi�;g Off.iciai. <br />Section 2116. <br />10. The boiler room shall have an agproved floor drain <br />or equvalent means for disposing of accumulation <br />, o£ li.quid caa�tes incident to cleaning or recharging. <br />Section 2119. <br />1 11, Provide air venting in compliance wi�h Section 2127 <br />�,�6�. <br />Permits will be issued upon receipt and approval of two (2) <br />sets of:•corrected drawings and specifications. <br />Yours truly . �. <br />Jamie Johnson, Inspection Supervisor <br />gy � le��-e l � � _ <br />hen Callahan _ <br />Plans Examiner <br />�7J:KC:eb . : s=•r--- t:.,._c�:.>_ v <br />. . _ , _ra ta;.�:aa�_ ..-_- ' -- <br />,o= ,--�.,� �---_ , <br />_- Ye_--- >> -- <br />- _--- ---=9� -�<__ , �.r <br />' . vi-l�tf--. �.v.....�_- :- ` <br />- <br />