Laserfiche WebLink
�e� <br /> � � <br /> ���� <br /> � <br /> F R A N K L i N �25 Fourth Avenuc PH 425 827-3324 <br /> Suite `L02 1=AX 425 827-6'L52 <br /> E N G I N E E R I N G Kirkland WA 98033 hvac@franV:lineng.eom <br /> MECHhNIChL rONSULTING <br /> C�G�1G S—G� � <br /> April 27, zooa ENVELOPE SUMMARY <br /> RE: MSRC - Seaway Bldg G <br /> Heated space applies to office space. <br /> Vertical Glazing: U=0.75, SC=1.0. Unlabeled glazing- 1/2" spacc Air, fi,ced, default. Or <br /> certified tested assembly per NFRC. <br /> Doors Type 1 (Opaquc, Exterior): Uninsulated metal, U=12, default. <br /> Other Roof Type L• R-11 rigid insulation on top of roof deck. U=0.08, calculated. <br /> Wall Type 1 (Opaque, Ex[erior, Floor to 9'-0" AFF): Concrete, min. 6" thick, furred with <br /> metal studs, 3-1/Z", 24" oc with R-11 batt insulation, U=0.1], calculated. <br /> Wall Type 2 (Opaque,Warchouse): Metal studs, min. 5-1/2", 24" oc with R-19 batt insulation, <br /> U=0.091, default. <br /> Wall Type 3 (Opaque, Exterior, 9'-0" AFr to Roo�: Concrete, min. 6" thick, with R-11 batt <br /> insulation stickpinned to concrete, U=0.09, calculated. <br /> Slab on Gradc: No Insulation, F=0.73, default. <br /> Please note that these values are minirn�um insulation for code compliance. Higher <br /> insulation values may 5e install�ed. <br /> SC = Shading Coeflicient <br /> ��(� <br />