.\ <br /> . <br /> �fhe tire t]oG� shall not bc less than 500 gpm, \ <br /> 3. The value obtained in Number 2 above may be reduced by up [0 50% for complete �' <br /> autoca[ic sprinkler protection. Where buildings are either fire resistive or non_ <br /> comhus[ible cons[ruction, and have a low fire hazard <br /> The percen[age reduction made for an automatic sprinkler�systemtuill dependUupon the <br /> extent [o which [he system is judged to reduce [he possibility of fires spreadine <br /> vithin and beyond the fire area. Normally [his reduc[ion will not be the maximuc� <br /> allowed withuuL proper sys[em supervision including va[er flow and valves. <br /> s[ructures exposedUwithini150 feet�byZthe�fire are�eunder considerationed This <br /> percer�tage shall depend upon the height, a�ea, and construc[io�� of [he buildin y <br /> being er.posed, the separation, openings in thP exposed buildin <br /> exposure, the provision of automatic sprinklers and/or outside sprinklers in [hes, ' <br /> buildin E�5) , [he length of � <br /> S�s) e�cposed, the occupancy of the exposed buildins<s) , and the effec[ of <br /> hillside locations on the possible spread of fire. <br /> The percentage for any one side generally shou]d not exceed tlie following limi[s <br /> foz �he separa[ions shown: <br /> Separation <br /> 0-10 feet Percentage <br /> 11-30 ZSX <br /> 31-60 ZD <br /> 61-100 15 <br /> 101-150 10 <br /> 5 <br /> The [otal percentage shall be the sum of the percentages for all sides, but shall <br /> , not exceed 75X. <br /> S• The ��alue obtained in No. 2 above is reduced by the percentage (if any) <br /> determined in No. 3 above and increased by [he percentage (iF any) determined in <br /> No. 4 above. _ <br /> The fire flow shall not exceed 12,000 gmm �or be less [han 500 gpm. <br /> No[e 1: The guide is not expec[ed to necessarily provide an adequa[e value for <br /> lumber yards, petroleum storage, refineries, grain elevators, and large <br /> chemical plants bu[ may indicate a minimum value for these hazards. <br /> Note 2; Judgment must be used for business, indus[riyl, and other occupancles <br /> not specifically mentioned. <br /> No[e 3: Considera[ion should be given to the configuration of the building(s) <br /> bei:ig considered and [o the fire departmen[ accessibility. <br /> Note 4: Flood frame s[ructures separa[ed by less [han 10 feet shall be consitiered <br /> as one fire area. <br /> ro[e S: Par[y Walls:- Normally an unpierced par[y (co�on) wall aay c•arrant up <br /> [o a lOX exposure charge. <br /> � <br /> . -z- <br />