Laserfiche WebLink
. . . ( � <br /> 4. Handrails for stainvays should bc shown on the drawings, per IBC 1012.1 Two handrails are required per <br /> IBC section 1009.1.2. <br /> 5. Handrail extensions at stairs should be shown on the drawings,per IBC section 1012.6. <br /> 6. Illuminated exit signs are required per IBC section 101 I.l. The exit sign locations should be shown on the <br /> drawings. <br /> 7. The means of egress should be illuminated at all times the building space is served by the means of egress, <br /> per IBC Section ]006.1. <br /> Upon submission of two insert sets of revised drawings reflecting the corrections requested,your application <br /> will bc processed. Applicable codes include the 20091ntemational Uuilding Code(IBC),the 20091ntemational <br /> Pire Code(IFC),the 2009 Intemational Mechanical Codc(IMC),the 2006 Washington State Energy Code <br /> (WSEC),the 2003 Accessible and Usable Duildings and facilities AI 17.1-2003 (ICC/ANS[). All codes <br /> referenced,as adopted by the City of Evcrett, should include current revisions by the State of Washington. These <br /> comments address building issues only. Revisions or additions may be required by other departments(such as <br /> Utilitics,Planning or Fire). <br /> All rcquired submittuls must be of sufficient detail and information to ensure that the proposed sWcture will be <br /> constructed in compliance with all adopted codes. You can rcach me directly to discuss this letter by e-mail at <br /> mh�le��Cn�ci everelt.wa.us or by phone at 425-2�7-8813. <br /> S' cerely, <br /> Meg li Icy,N RB <br /> Plans E amincr <br /> 'a�a <br />