Laserfiche WebLink
��i L. <br /> f,���.� t� <br /> :,U�usi 27, ly7i <br /> .^:1 Da�-�et� <br /> Re : Steppir.�:�ol^o <br /> Everett, ?•JasninEton <br /> Dear Sir: <br /> In a recer.i inspection of your tavern we :ound the following discrepancies: <br /> 1. ;he bo=lor room was not one hour constrLction. This can be taken <br /> ce:e o� by: <br /> (A)Tappi.:�g ali soams nct on studs. <br /> (E)Fi�cing vent in ceilinR with fire damper or ducting to the outside. <br /> (C) Install a closor and latch on the door. <br /> 2. ;9ir.or electrical discrepancios were noted. This requires: <br /> (A)';lire nuts end faston fixtures in the boiler room. <br /> (3)Covor plate installed on ol3ctrical plug in the rear of the pool area. <br /> 3, rJ:IP requiromonts wore not met, This requires: <br /> (A)110 occupancy load-requires two r.XIT doors. <br /> (I3)EXIT doors to swing outward. <br /> (C)rXIT doors to hav�� pani.c hardware <br /> (D)P.11 roquired EiCITS requiro lighted EXIT signs. <br /> 4. Seneration from storage to assembly not one hour. This requires: <br /> (A)Solid core doors with closers and latch. <br /> (B)5�t� " sheet rock on all walls from floor to cailing betwaen <br /> stora6e and assembly areas. <br /> 5. Bl�.inguishers iaore not adequate. This requires: <br /> (A)Gne 2A rated extinguisher in the bar area. <br /> Si�erely yours, � <br /> / <br /> � �� �,l��-�f%G" <br /> i•lalter H. Cooper <br /> r ire I�arshsl <br />