Laserfiche WebLink
C,r �aJ <br />Is the area where the container is to be installed well lighted? BSG Required <br />Initial <br />2.2.3. <br />Containers shall be provided with substantial concrete or masonry foundations, <br />or structural steel supports on firm concrete or masonry foundations. <br />(Sea Article 7501.I.a oi ttw UnNam Fire Cada) <br />(Sae Also C(iA P-78 Section 6.1.1) <br />Does the soil have a minimum 2000 PSF bearing capacity? BSG Required <br />Initial <br />2.2.3.1. 450 L Pad Reauirements <br />Is a steel plate base included? eSG Aequired <br />The pad, container, and steel plate base shall be constructed and assembled in <br />the following manner: <br />1. Steel tank is attached to plate base with welding. <br />2. Add concrete pad: <br />a. Reinforced 6" thick x 3'-2" square concrete pad <br />b. Pad reinforced with 3-#4 bars x 2'-8" each way mid depth of pad <br />c. Concrete shall be F'c 25Q0 PSI, 28 day strength minimum <br />d. Reinforcing steel shall be Grade 60 minimum <br />3. Attach plate base to concrete pad. <br />Provide four'h" diameter expansion bolts, Kwik Bolt II, into drilled <br />holes per manufacturer's recommendation, embed 3 1/2" and provide 7" <br />minimum edge distance. <br />Initial <br />2.2.3.2. 1000 L Pad Re�c ufrements <br />Is a steel frame base included? esG Required <br />The pad, container, and steal frame bas:: shall be constructed and assembled in <br />the fa;lowing manner: <br />1. Attach steel tank to frame base. <br />F:�compeny�Slendards • BSO�enpinaerirp stendardclanpineerinp atendards in devabprn�nNnat P�mia lnatall <br />ChedclisLdoc �y�+ <br />