Laserfiche WebLink
4. A firc hy�rant is required within 200 driving fcet, but not closcr than �0 feet, of c��cry <br />structure. Locaiion of the hydrant(s) shall be approved Uy the fire Marshal. <br />`. I3ascd upon 7,792 squarc fcct of 1'ypc V-B, sprinklcred construction, the iire ilow <br />requircmcnt is 1,500 gpm. <br />G. I�ire Alarm Systcm - Au appro��cd autontatic firc detection system shall be providcd as <br />requircd by City Ordinance No. 1IO2-92, Chaptcr 16.7G, of the Evcrett Municipal Code. Plans <br />for such systcro shall bc submittcd to thc Pirc I�larshai for re�ic�v and approval prior to <br />installation. Submivai shall includc cut sheets of all equipment intcnded for usc. Appropriate trip <br />tcsts, ���imesscd by a Pire Deparunent insrector, shall be perforuted, along ���idi a certificate of <br />complciion, prior to final acceptauce of the systetn. Pire alarm systems shall be installed <br />according to NPPA Standard 72. Inst:�llation of �rc alarm componculs, including basic <br />���iring, may� nol connuence before pl.ms are appro��ed b�� thc rire Department Plan <br />Rc��ic���cr. Pirc alarm dra���ings must bc proCcssionaily rcndcred, ��� s�rr,����u a�«�i, and nmst bc <br />intcrnally consistcnt. Riscr Ji:igrams must matcl� installation plans and load calculations. <br />Componcnts must bc listed vid appro��cd Ibr usc together. Changes ro plans must include new <br />dra���ings and calculations and must bc approveJ bp thc �ire Department Plan Rcviewer prior tu <br />installation. Pire alarm installation is subject to Celd inspection by a Pire Department Inspector. <br />An appro��cd sct of plans .md Uic I3uilding Deparhncnt clecn'ical permit must bc present for any <br />in�tallation inspection. Pire alarm s��stems shall bc installed uuder permit of the City of Lverett <br />13uilding llcp:utmcnt. 6lrctrical inspcctions .ind :�pproval arc myuired prior to calling for <br />.iccepumcc tcsts. Call (42J1 257-R310 for permit information. Thc abscucc of �corking pltone <br />lincs 1'or Uie alarm s}�stem «ill bc cause fm• postponing tire deE�nrtment inspcction and testing <br />and shall result in dcninl of occupanc�'. <br />7. Pire Sunnression (S�irinklcr) SVstcm - An approved automatic suppression systcro s6all bc <br />provided as rcyuircd by City Ordinancc No. 1902-92, Ch.�Ptcr 1G.76, of thc Evcrett Municipal <br />Cude. 'Clie s�•stem must include a meclianical ��•ater gong bell. Plans for an�� such system shall <br />be submittcd to tlic I3uilding Depariment for cxaminauon and approvaL Such plans shall include <br />plans for thc undcrground mains tliat ���ill supply the sprinkler system. 'Che type of sprinkler to be <br />installed �eill be determined by tlie E3uilding Officia�. It may be an NPPA 13, NFPA 13R, or <br />NPPA 13D system depending upon se��eral factors. 5prinkler installation shall not Uegin �viQiout <br />an approved and stampcd sct of plans from the Duilding Department. The Pire Dcpartment will <br />also re��iew the plans and shall ficld inspcct the installation based ottly on approved plans that must <br />Ue on site. Changcs to plans nmst be approvcd by both the Building and Pire Departments. <br />AUoveground sprinkler piping shall be hydrostatically tested as estab(ished in NFPA Standard 13. <br />Llnderground piping shall bc Ip�drostatically tested and flushed as establisl�ed in NFPA Staudard 24 <br />for privale fire mains. (Bclow-�;round uinint; must bc instnlled bv �i'ashinelon Stnte Pntrol <br />Licensed Uuder�round S��rinkler liue ccrtificd °U" installcrs, Tor furQier information, <br />coutact thc State rire Mn:shal's Officc at (360) 570-3134 or contact Nie Gverett Fire <br />Ucpartment at (425) 257-8123.) All such rests shall be witnessed by a fire Department <br />inspcctor. Call (425) 257-8124 to make an appointment for inspection. Contractors' material� and <br />