Laserfiche WebLink
4. A fire hydrant is rcquired �vithin 200 driving feet, but not doscr than 50 fcet, of every <br />su•uclure. Location of lhe hydrant(s) shall be approved by the Fire Marshal. <br />5. I3ased upon 7,792 square fect of Type V-B, sprinklered construction, the firc ❑ow <br />requirement is 1,500 gpm. <br />6. Pirc Alarm Svstem - An approved automatic tire detcciion systen? shall bc pro��idcd as <br />rcyuircd by City Ordinance No. 1902-92, Chaptcr 16.76, of the E��erett Iviunicipal Code. Plans <br />for such systcro shall Ue submilted �o thc Pirr Marshal for revic��� aud approval prior to <br />installation. Submittal shall indudc cut shccts of ail cquipment intcnded for usc. Appropriate trip <br />tests, wiuiessed by a Pire Deparuuent inspectur, shall be performed, along with a certificate of <br />comi�Iction, prior to tinal acceptancc of the system. Pirc alarm s}stems shall Ue iustalled <br />according to NI�PA Standard 72. Inst:illatiou of firc alarm componcnts, iucludiug basic <br />�viriug, ma�' not commence before plans are appro��ed I>V the Fire Department Pl�n <br />Rc��ie��•a•. Pirc alarm dra�aings must hc profcssionaily rcndcred, in sufticicnt detail, and must be <br />intcrnally cousistcnt. Riscr diagrams : mst match installation plans and Ioad calculations. <br />Componcnts must hc listcd and approecd for use �ogciher. Changcs to plans nmst indude ne�v <br />drawi»gs and calculations and must be approveJ by the Pire Department Plan Re��iewcr prior to <br />installation. Fire al<irm installation is sttbject to field inspection bp a Fire D�partment Inspector. <br />An appro��ed set of plans and the I3uilding Deparuncnt clectrical permit must he ittesent far an�. <br />instaliation inspcction. Pirc alarm systems shall bc instailed under pennit of thc City of B��crett <br />13uilding Department. Giectrical inspections and approval arc required prior to calling for <br />acccptancc tcsts. Call (d25) 257-8510 for permit information. '1'hc absencc of �ti�orking phonc <br />lines fm• the alarm s��stem will be c:iuse for postpaning fire department inspectim� and testing <br />:u�d sl�all result iu dcuial of occup:mcy�. <br />7. �ire Sunt�ression (Snrinkler) S1'stcm -:1n appro��ed automatic suppression system shall be <br />provided as rcyuired by City Ordinancc No. 1902-92. Clia�ter 16.7G, of the Gverett Municipal <br />Codc. The syste�u musl include a mech:uiical ��•aler gong bell. Plans for any such system shall <br />bc submittcd lo tlie Duilding Deparunent for ezamination and approval. Such plans shall indude <br />plans for Uic underground mains tliat will supply the sprinkler s��stem. The type of sprinhler to be <br />iitstalled ���iil bc dctermincd by thc Building OfficiaL It may be an NPPA 13, NFPA 13R, or <br />NrPA 13D s)-stcm depeuding upon sc��eral factors. Sprinklcr installation shall not begin wi[hout <br />an approved and stampcd set of plans from tl�e [3uilding Deparmient. Thc Firc Dcpartment will <br />also rcview the plans and shall ficld inspcct thc installation bascd only on approved plans Uiat must <br />bc on site. Changes to plans must Uc approved by both the Building and Fire Departments. <br />Abo��eground sprinkler piping shall bc hydrostatically tested as established in NPPA Standard 13. <br />Underground piping shall be l�pdrostatically tcsted and Ilushed as established in NFPA Standard 24 <br />tor privatc fire maitis. (I3elo«�-Lrouud I�iP���C must be iustalled bV �'VashinEtm� State Patrol <br />I icensed Undcr�rouud SDrinkler line certi�ed "U" installers. For further informntion, <br />contnet tlie State Tire A4arshal's O�fice at (3G0) 570-3134 or contact the Everett Fire <br />Department at (d25) 257-8123.) All sucl� iests shall Ue witnesscd Uy a Fire Departmeut <br />inspcctor. Call (425) 257-R124 to make an appoinunent for inspection. Contractors' materials and <br />